SYMPTOM POSSIBLE CAUSE - SUGGESTED ACTION
Dew Point too
low
The fan is always on – verify the correct operation of the fan power contactor (see
KV1/KV2 on the electric diagram) and/or of pressure transducer (see BHP on the
electric diagram) – (Air-Cooled).
Ambient temperature is too low - restore nominal conditions (Air-Cooled).
The hot gas by-pass valve is out of setting - contact a refrigeration engineer to
restore nominal setting.
Excessive
pressure drop
within the dryer.
The dryer doesn’t drain the condensate - see specific point.
The DewPoint is too low - the condensate is frost and blocks the air - see specific
point.
Check for throttling the flexible connection hoses.
The dryer
doesn’t drain
the condensate
The condensate drain service valve is closed - open it.
Verify the electric wiring.
The DewPoint is too low - the condensate is frost and blocks the air - see specific
point.
Inlet compressed air pressure is too low and condensate is not drained – restore
nominal conditions.
Electronic drainer is not operating correctly (see paragraph 7.16).
The dryer
continuously
drains
condensate.
Electronic drainer is dirty (see paragraph 7.16).
Water within the
line.
The dryer doesn't start - see specific point.
If installed - Untreated air flows through the by-pass unit - close the by-pass.
The dryer doesn’t drain the condensate - see specific point.
DewPoint too high - see specific point.
HPS high
pressure switch
has been
activated.
Check which of the following has caused the activation :
1. The ambient temperature is too high or the room aeration is insufficient - provide
proper ventilation (Air-Cooled).
2. The condenser is dirty - clean it (Air-Cooled).
3. The condenser fan doesn’t work - see specific point (Air-Cooled).
4. The cooling water is too hot - restore nominal conditions (Water-Cooled).
5. The cooling water flow is insufficient - restore nominal conditions (Water-Cooled).
Reset the pressure switch pressing the button on the controller itself - verify the
dryer for correct operation.
HPS pressure switch is faulty - contact a refrigeration engineer to replace it.
LPS low
pressure switch
has been
activated.
There is a leak in the refrigerating fluid circuit - contact a refrigeration engineer.
The pressure switch reset automatically when normal conditions are restored -
check the proper operation of the dryer.