Technical data

Technical description
ACT 600 – 5000 25 – EN
7.15.1 How to switch on the dryer
When the unit is powered the display shows
.
The condensate drain test is always active through button
ESC
.
Press
for at least 2 seconds to start the dryer: if the compressor has been shut down for enough time, it
will start up immediately; otherwise the display will show the countdown of the seconds before the
compressor starts up again, and the led
flashes (max delay 5 minutes).
7.15.2 How to switch off the dryer
From any menu press
for at least 2 seconds. The display shows .
7.15.3 How to display the operating parameters – INFO Menu
The info menu shows the dynamic operating parameters of the dryer.
With the dryer ON and not in other menus, press
info
for at least 1 second to enter the info menu.
Access to the info menu is confirmed by message
on the display (first parameter of the menu). Use the
arrows
and to move to the following/previous. Press
info
to show the value of the selected
parameter. Press
info
again to return to the list of displayable parameters.
Press
ESC
to exit info menu (if no button is pressed after 2 minutes the menu is exited automatically).
Info Description
T1 - Temperature probe T1 – DewPoint
T2 – Temperature probe T2 – Air IN
T3 – Temperature probe T3 – compressor suction
T4 – Temperature probe T4 – compressor discharge
HP – condensing pressure HP
HrS – total hours of operation
SrV – hours until next service
Note :
The temperatures are displayed in °C or °F (led
or is lighted).
Pressure is displayed in barg or psig (led
or is lighted).
The total hours of operation and the hours until the next service are shown in the field 0…999 hours
and in thousands of hours from 01.0 hours on (example : if the display shows number 35 it means
35 hours; if the display shows number 3.5 it means 3500 hours).