Technical data
Technical description
22 – EN ACT 600 – 5000
7.10 Capillary tube
It consists of a piece of reduced cross section copper tubing located between the condenser and the
evaporator, acting as a metering device to reduce the pressure of the refrigerant. Reduction of pressure is a
design function to achieve optimum temperature reached within the evaporator: the smaller the capillary
tube outlet pressure, the lower the evaporation temperature.
The length and interior diameter of the capillary tubing is accurately sized to establish the performance of
the dryer; no maintenance or adjustment is necessary.
7.11 Alu-Dry module
The heat exchanger module houses the air-to-air, the air-to-refrigerant heat exchangers and the demister
type condensate separator. The counter flow of compressed air in the air-to-air heat exchanger ensures
maximum heat transfer. The generous cross section of flow channel within the heat exchanger module leads
to low velocities and reduced power requirements. The generous dimensions of the air-to-refrigerant heat
exchanger plus the counter flow gas flow allows full and complete evaporation of the refrigerant (preventing
liquid return to the compressor). The high efficiency condensate separator is located within the heat
exchanger module. No maintenance is required and the coalescing effect results in a high degree of
moisture separation.
7.12 Hot gas by-pass valve
This valve injects part of the hot gas (taken from the discharge side of the compressor) in the pipe between
the evaporator and the suction side of the compressor, keeping the evaporation temperature/pressure
constant at approx. +36°F (+2°C). This injection prevents the formation of ice inside the dryer evaporator at
every load condition.
ADJUSTMENT
The hot gas by-pass valve is adjusted during the manufacturing testing phase. As a rule no
adjustment is required; anyway if it is necessary the operation must be carried out by an
experienced refrigerating engineer.
WARNING
the use of ¼” Schrader service valves must be justified by a real malfunction of the refrigerating
system. Each time a pressure gauge is connected, a part of refrigerant is exhausted.
Without compressed air flow through the dryer, rotate the adjusting screw (position A on the
drawing) until the following value is reached:
Hot gas setting : R407C pressure 65.3 psig (+1.45 / -0 psi) [4.5 barg (+0.1 / -0 bar)]
ACT 600 – 1250
2 x
A
4 mm
5/32 in.
+
-
V
L
Y
0
0
0
1
ACT 1500 – 3000
A
8 mm
5/16 in.
-
+
V
L
Y
0
0
0
3
ACT 3750 – 5000










