13.9 TCP/IP Bootstrap Protocol (BOOTP)
Since firmware 4.3, eWON is BootP manageable.
You can force eWON to ask its IP address to a BootP Server.
To correctly set the IP mask and the Gateway, your BootP server must comply with the RFC-1048.
Figure 83: Ethernet Setup Page
At each startup, eWON will receive its IP address from the Server.
eWON will wait for the server unless it is not present.
eWON will perform a new attempt at encreasing interval (1 minute interval max.) endlessly.
While waiting for its IP address, eWON is in startup phase and thus it is not functioning! During this time, eWON will blink
continuously the USER LED with the following pattern:
Resolution:
1) Pushing on the Reset button (on the front face from the eWON) will skip the BootP request, then eWON will use the IP address which
is configured in the Ethernet configuration page
The Duplicate IP test is skipped too!
2) Make a Second Level Reset (see chapter “Second level reset” on page 227) to force eWON to 10.0.0.53 IP address and to disable
the BootP mechanism
eWON is now accessible.
short red light + pause + long green light + pause