13.7 Table of comparisons between eWON types
13.8 Duplicate IP detection (User Led blinking Red)
Since firmware 4.3, eWON performs a check on the IP network in order to avoid duplicate IP.
eWON makes this test at power up to see if its IP address is not conflicting with another device.
If eWON is configured with the same IP address than another device, eWON will not start and the USER LED blinks continuously
with the following pattern:
Resolution:
1) Isolate your eWON from the conflicting device
The best way is to use a direct crossed IP cable to directly link your PC with the eWON (without a hub)
2) Reboot the eWON
3) Change the eWON IP address (with eBuddy, you can download from http://www.ewon.biz
Support/Download Software)
When eWON is blocked, the duplicate IP test is made again every 10 minutes. If the conflicting device is not present anymore, then
eWON will start normally.
Feature eWON 500 eWON 2001 eWON 4001 eWON 4002
“Dial up (PPP)” on page 42 NO (no modem) YES YES YES
“Callback” on page 45 NO (no modem) YES YES YES
“PPP Dump” on page 34 NO (no modem) YES YES YES
“COM Setup section” on page 35 NO (no modem) YES YES YES
Historical Data Logging
NO NO YES YES
“
Tag main edit window” on page 59
Real Time Logging
NO NO YES YES
“
Tag main edit window” on page 59
“Modem” on page 37 NO (no modem) YES YES YES
“Router” on page 48 NO (no modem) YES YES YES
“SMS on alarm configuration” on page 65 NO (no modem) YES YES YES
Table 154: Features available depending on the eWON type
short red light + pause + long red light + pause