User guide
eWON 500-2001-4001-4002 User Guide - Upgrading the eWON firmware
eWON 500®2001®4001®4002® Version 4_3_0 - User Guide - 10/5/05 - ©ACT'L sa - Page 224
• Click on the “Disconnect” icon to exit the connection to the eWON and quit the SmartFTP program.
WARNING:
When you click on the “Disconnect” icon, the eWON begins a flash memory programming operation (about one minute long).
Do NOT remove the power from the eWON during this operation.
If you have a look at the eWON STATUS led, it will be blinking about once a second.
When it finishes blinking, the eWON will reboot.
The reboot operation can be observed on the Ethernet link led, going off and then back on again.
Please do NOT remove power until you can get access to the eWON using your web browser of FTP browser.
Failure to do so can lead to the destruction of the eWON and a factory return would be unavoidable.