The MbsBits parameter specifies how to Modbus IO Server will read the bytes. The possible values are 7 and 8 bits/byte.
9.5.2 Com Section
This section describes the fields found in the comcfg.txt file. All the fields are readable and writable (unless otherwise specified) using GETSYS
and SETSYS with the COM parameter.
Example:
Setting the First ISP phone number (parameter = PPPClPhone1) to number 0123456789:
MbsSIP(x) x=1..3, Modbus Topic x IP address IO Server Config Æ Modbus
FtpServerPort FTP Server port System Setup/General/General
FtpServerAddr FTP server address System Setup/General/General
FtpUserName FTP login name System Setup/General/General
FtpPassword FTP password System Setup/General/General
SmtpAllowB64
MbsEn(x) x=1..3, Modbus Topic x enabled (1 if enabled, 0 otherwise) IO Server Config Æ Modbus
FTPC_SDTO
FTPC_SCTO
FTPC_ACTO
FTPC_RDTO
DNS_SRTO
SnmpCom(x) x=1..5, SNMP Community x System Setup/General/SNMP
SnmpR x=1..5, SNMP Community x Read enabled System Setup/General/SNMP
SnmpW x=1..5, SNMP Community x Write enabled System Setup/General/SNMP
SnmpAlwAll Accepts SNMP packet from any host (1 = enabled) System Setup/General/SNMP
SnmpHIp(x) x=1..5, SNMP Host x IP Address System Setup/General/SNMP
SnmpHCom(x) x=1..5, SNMP Host x Community System Setup/General/SNMP
SnmpHTrap(x) x=1..5, SNMP Host x Trap enabled System Setup/General/SNMP
SnmpHAlw(x) x=1..5, SNMP Host x access allowed System Setup/General/SNMP
MbsBits* Modbus Bits (7 or 8) N/A
AlMaxTry Number of times an action is retried in case of error System Setup/General/General
AlRetryInt Interval between action trials in case of error System Setup/General/General
SETSYS COM, "LOAD"
SETSYS COM, "PPPClPhone1",0123456789
SETSYS COM, "SAVE"
Table 103: system configuration fields