System information

General Reference Guide IO Servers Configuration
RG-001-0-EN ver 1.5 eWON® - 20/03/2009 - ©ACT'L sa Page 97
Important: When there are multiple IO servers potentially using the serial line, the unused IO servers must be "DISABLED" for the
unused IO server baudrate.
Example: if Modbus and UniTE IO servers are available, at least one of them must have the baudrate configured to "Disabled". If
not, one of the IO servers will not be able to use the serial line and it will be disabled, with an error written in the event log.
5.5.2.2 Topic configuration
Figure 80: XWAY-UNITELWAY topics configuration
Three topics can be used for the IO Server. These topics are used to give a common property to a group of UNITE Tags such as:
• Enable/Disable
• Poll rate
• Global Slave address
5.5.3 Tag name convention
The Item Name can contain the PLC address where the value is polled, or not. If the address is also specified at topic level, the address specified
at Tag level will be ignored. If the Topic address is not defined either, then address 0,254,0 will be used.
Topic configuration item Description
Topic enabled Enables or disables polling of all the Tags in the topic.
Global Slave Address
This Slave address is a global parameter for all the Tags of the topic. See below for the Device
Address syntax. If an address is specified here, it will replace (overload) the address defined Tag by
Tag.
Poll rate
Defines the refresh rate of the Tag name. In a complex application, we can imagine that some Tag
name must be refreshed every second – typically for digital input - and other every minute – typically:
temperature-.
Table 69: UNITE - topics configuration
IO Server configuration
IO Server Name UNITE
Topic Name
A
B
C
Item Name
ValueName,Network,Station,Gate,Module,Channel
PLC Address is defined Tag by Tag (and the gate requires a
5 level addressing)
ValueName,Network,Station,Gate PLC Address is defined Tag by Tag
ValueName Topic PLC Address is used
Table 70: UNITE - IO server configuration