5.3.2.4.1 Additional advanced parameters
• gwdestaddr
When the eWON is used as a Modbus gateway, it uses the UnitID from the ModbusTCP request to determine the Modbus RTU destination
address.
It is possible to bypass this mechanism and force all the requests received by the eWON in ModbusTCP to be forwarded to a single ModbusRTU
device (EXCEPT for requests with UnitID corresponding to the eWON's Modbus TCP Unit address (usually 100) when the eWON Server is
enabled - see explanations about this precise point in the above configuration fields descriptions).
Every request is forwarded to the device with Slave address defined by the Modbus IO server advanced parameter called gwdestaddr.
If the advanced parameters textfield contains the following entry:
gwdestaddr:10
Then all therequests will be forwarded to the slave with address 10.
REMARK: the eWON will change the address before sending the request to the slave, then it will change it back when sending the response to
the master (Modbus TCP master). So the gwdestaddr will never appear in any communication between the Master and the eWON.
• FastSrv
FastSrv is a mode which allows a supervisor to read in Modbus TCP more easily the Modbus tags published by the eWON. This mode completely
changes the tag’s addressing, and when activated, the Modbus addresses are no more compatible.
You have just to enter “FastSrv:1” in the Advanced Parameters text area to activate it. When done, the Modbus tags can be read as follows:
Notes:
• If the tag is binary read, its value is worth 0 if tag==0, and 1 if tag <>0
• Writing 0 in AlarmStatus acknowledges the alarm (will be logged by eWON as acknowledged by administrator)
• It is not possible to write a coil in the float area (coil address range: X+2048 to X+4094)
• It is not possible to address more than 1024 registers in float.
Click on the Update Config button to validate your inputs or use the Cancel button to discard changes
• TcpPort
Use the 'TcpPort' parameter to change the default 502 port used when the eWON is ModbusTCP CLIENT.
If not specified the 502 default value is used.
This Port value is used for all the ModbusTCP client connections.
Parameter name Description
PreDelayFrom
Used in conjunction with the next parameter (PreDelayVal), starting at that slave address, the eWON will
insert a delay when switching from one slave address to another. If the PreDelayVal feature is not used,
then the value for PreDelayFrom must be set to 256 (default value).
PreDelayVal
Used to define the delay (in Msec) to be inserted before a request to a slave if a request was previously
sent to another slave address (not between 2 requests to the same slave).
The PreDelayVal is placed only for slaves with an address higher than PreDelayFrom.
ErrorRetry Defines the number of errors before the device enters in slow poll mode. (Minimum 1)
SlowPollSkip
Defines the number of times the slave is skipped when in slow poll mode. This delay depends on the poll
rate.
GatewayIPCTimeout
Maximum event lock while waiting for a response to a modbus gateway request from the modbus IO
server (router) (in Msec – minimum 1000).
PostErrorDelay
This delay (in Msec) is added each time a device responds with a framing error or a CRC error, in order to
help the bus to perform its re synchronization (default value = 50).
MaxDeltaCoilX (X= A,B,C) Maximum number of Coils that can be grouped in a request (per topic) max=256
MaxDeltaRegX (X= A,B,C) Maximum number of registers that can be grouped in a request (per topic) max=124
Table 58: extended IO server configuration controls
X Integer (with scale factors and offset defined)
X+2048
Float (X+2048: 1
ST
float, X+2048+2: 2
nd
float, etc.)
X+4096 Alarm status
X+6144 Alarm type