System information
General Reference Guide IO Servers Configuration
RG-001-0-EN ver 1.5 eWON® - 20/03/2009 - ©ACT'L sa Page 86
5.2.1 IO Server Clear
To avoid the useless consumption of CPU and memory, the unused
IO Servers need to be “unloaded” from CPU tasks and the used
memory need to be cleared.
For that purpose, the Clear function must be used.
Only set to disable the BaudRate of an IO Server make it idle, but this
IO Server is still in memory and use some CPU time (for nothing).
Click on the Clear link to reset the config of the displayed IO Server
and unload it from memory.
Some IO Servers are not dynamically stoppable and need an eWON reboot to ensure the unload from memory. You will be warned with the
following message.
5.2.2 IO Server Init
Click on the Init link to initialise an IOServer.
This initialisation will reset all IOServer counters (See “Status” on
page 159) and restart the tags validation process (See “Tags
validation” on page 68).
5.2.3 Global Config
Figure 72: IOServer Global Config page
Item Description
Modbus TCP Port Encode here the TCP Port number used for the ModbusTCP server protocol. Default is 502
Ethernet/IP Port Encode here the TCP Port used for the Ethernet/IP protocol (Allen Bradley). Default is 44818
ISOTCP Port Encode here the TCP Port number used for the ISOTCP protocol (Siemens). Default is 102
FINS Port Encode here the TCP Port number used for the FINS protocol (Omron). Default is 9600
Disable Tags in Error Activate the Tags Validation See “Tags validation” on page 68