System information
General Reference Guide eWON Configuration
RG-001-0-EN ver 1.5 eWON® - 20/03/2009 - ©ACT'L sa Page 25
3.3.3.4 Debug
Figure 22: Debug configuration page
Control Description
Log Incoming call Logs communications when the eWON is acting as a PPP server
Log Outgoing call Logs communication when the eWON is acting as PPP Client (connects to a server)
Log Size (bytes)
Number of bytes allocated for logging PPP communications.
When the log is full, logging stops (this does not prevent communication from continuing)
Maximum log size is 1MByte (Log Size between 50000 and 100000 are sufficient for debug purpose)
Append to log
Prior to append to log, you must clear log manually using the Clear Log button in the PPP Dump
configuration page
Log following connections
The eWON will log only the N next connections, the number of connections will be decreased each time
a new connection is logged. When the last connection has been logged, then the counter will be set to -1
(to prevent further connections to be logged).
When the value of this counter is 0, then all connections are logged.
You can manually set the counter to -1, in order to suspend connection logging, but if you want to release
the log buffer, then you should disable the Log Incoming call and the Log Outgoing call options.
In case you want to log multiple connections, you can choose to Append data to the log or not.
clear log now Clicking on this button will clear the PPP dump log.
Table 16: PPP dump configuration controls
Control Description
Debug COM (1..4)
Set the debug mode of the Serial COM ports (1 to 4 depending of the eWON type).
All the debug information will be available in the Real Time Log page (See "Real Time Log" on page 161)
Choose between following mode:
• No debug: no debug information logged (default)
• HEX on RX/TX: Log hexadecimal data received and transmitted
• HEX and ASCII on RX/TX: Log hexadecimal and ASCII data received and transmitted
• HEX and ASCII (no timeout): Log hexadecimal and ASCII data received and transmitted, without
timeout information (clearer log)
Debug ADSL
Only available on eWON2104 or eWON4104.
Log ADSL trace in the ADSL log page (See "ADSL Log" on page 163)
Error Debug Append hex location data to logged events
Table 17: Debug configuration controls