System information

General Reference Guide eWON Configuration
RG-001-0-EN ver 1.5 eWON® - 20/03/2009 - ©ACT'L sa Page 14
3.3.1.2 Alarms (globals parameters)
Figure 11: eWON system general setup – Alarms
After having encoded your parameters, go to the bottom of the page to .
3.3.1.3 Date & time
Figure 12: eWON system Date & time setup
The eWON’s real time clock can be updated manually with this dialog window. Fill in the edit box with date and time and click on .
An event will be added to the event log indicating the time update and the time offset between old and new time.
Important: Updating the time may result in duplicate points stored in non-chronological order in the eWON files (alarms,
events and historical).
Control Description
Action retrig interval
If an alarm is still present after this interval, then a new action on alarm will be triggered once (only if the alarm
condition is still true AND if the alarm has not been acknowledged yet). The default value for this parameter is
one day (86400 seconds).
Try action
This parameter defines the number of times the action will be retried in case of errors. The value of this number
must be greater than 1.
Action retry interval
This parameter defines the interval between two actions attempts if an error occurs. The value for this parameter
must be greater than 10.
Table 6: global alarms controls