System information

General Reference Guide IO Servers Configuration
RG-001-0-EN ver 1.5 eWON® - 20/03/2009 - ©ACT'L sa Page 122
5.10.2.3.2 PT100 input AI5 and AI6
These two entries measure a Resistance value in Ohm.
As you can see, the slope is negative, and if you need to read the Tag value converted in Ohm, you can set a factor of -0.02014774 = -82.505/
4095 with an offset of 162.13.
Figure 94: Tag’s configuration: reading the tag value in Ohms
If you need to convert into °C: temperature = AI * (-0.0523311) + 161.376.
The default range of PT100 in eWON is -50°C to 150°C.
Full range of ADC is: -52.92°C to 161.376°C (79.625 Ohm to 162.13 Ohm).
Note:
• eWON 4002 models prior to S/N 0517-xxxx-89 have a PT100 range from 0°C to 131.9°C and must apply the following formulas:
Ohm = IOValue * (-0.012402) + 150.8
°C = IOValue * (-0.0322) + 131.9
• eWON 4002 models from S/N 0517-xxxxx-89 to S/N 0521-xxxx-89 have a PT100 range from -56°C to 151°C and must apply the
following formulas:
Ohm = IOValue * (-0.0195068) + 158.2
°C = IOValue * (-0.050677) + 151.2
AI# Ohm
0 162.13
4095 79.625