Specifications
GENERAL DATA - HEAT PUMP R410A INVERTER
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 12°C / 7°C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35°C AIR AMBIENT TEMPERATURE.
b) HEATING - 40°C / 45°C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7°C AIR AMBIENT TEMPERATURE.
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
56
A5ACV210CR
Btu/h
200000
W 58562
Btu/h
210000
W
61490
COOLING W 22300
HEATING W
21800
COOLING A 44.6
HEATING A
44.6
V/Ph/Hz
380-415 / 3 / 50
R410A
ELECTRONIC EXPANSION VALVE
HEIGHT mm/in 1786 / 70.3
WIDTH mm/in
2093 / 82.4
DEPTH mm/in
1192 / 46.9
HEIGHT mm/in 1975 / 77.7
WIDTH mm/in
2176 / 85.6
DEPTH mm/in 1300 / 51.2
kg/lb
642 / 1415
dBA
85
COOLING
l/s / m
3
/hr
2.7 ( 9.6 )
HEATING
l/s / m
3
/hr
2.9 ( 10.3 )
PROPELLER / DIRECT
2
HORIZONTAL MULTISTAGE END-SUCTION
MAX. WATER OPER. PRESSURE kPa / psi 1000 / 145
COOLING
l/s / m
3
/hr
2.7 ( 9.6 )
HEATING
l/s / m
3
/hr
2.9 ( 10.3 )
INSTALLATION PIPE CONNECITON mm/in
38 / 1 1/2
COOLING m
25.0
HEATING m 25.0
NOT APPLICABLE
L / ft
3
NOT APPLICABLE
SCROLL
0 - 210000
COOLING kg/lb 9.5 / 20.9
HEATING kg/lb
8.5 / 18.7
PIPING
TYPE
COMPRESSOR
HEAD
MATERIAL
REFRIGERANT
STAGE OF CAPACITY CONTROL (Btu/h)
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
POWER SOURCE
CONTROL
CAPACITY/VOLUME
UNIT DIMENSION
PACKING DIMENSION
TANK
NOMINAL WATER FLOW
UNIT WEIGHT
PUMP
TYPE
WATER FLOW RATE
HYDRAULIC KIT
CHARGING MASS
MODEL
TYPE/DRIVE
QUANTITY
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
REFRIGERANT TYPE
EVAPORATOR
CONDENSER FAN
SOUND PRESSURE LEVEL