Specifications
85
GENERAL DATA - R410A HEAT PUMP
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151 & ISO13253.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 12°C / 7°C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 35°C AIR AMBIENT TEMPERATURE.
b) HEATING - 40°C / 45°C ENTERING / LEAVING EVAPORATOR WATER TEMPERATURE, 7°C AIR AMBIENT TEMPERATURE.
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND 1m BELOW THE UNIT.
A5AC20CR A5AC25CR
Btu/h
15,700 19,400
W
4610 5690
Btu/h
21500 25000
W
6300 7330
COOLING W
2620 2830
HEATING W
2590 2790
COOLING A
11.9 12.7
HEATING A
12.1 12.9
V/Ph/Hz
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
HEIGHT mm/in
WIDTH mm/in
DEPTH mm/in
kg/lb
128 / 282 128 / 282
dBA
58 59
COOLING
l/s / m
3
/hr
0.24 / 0.86 0.28 / 1.00
HEATING
l/s / m
3
/hr
0.32 / 1.16 0.35 / 1.25
11
MAX. WATER OPER. PRESSURE kPa / psi
COOLING
l/s / m
3
/hr
0.24 / 0.86 0.28 / 1.00
HEATING
l/s / m
3
/hr
0.32 / 1.16 0.35 / 1.25
INSTALLATION PIPE CONNECITON mm/in
COOLING m
9.0 9.8
HEATING m
7.3 9.0
L / ft
3
ROTARY ROTARY
0 - 100% 0 - 100%
kg/lb 1.2 / 2.7 1.7 / 3.8
NOMINAL RUNNING CURRENT
R410A
1000 / 145
25.4 / 1
POWER SOURCE
CONTROL
CAPILLARY TUBE
220-240 / 1 / 50
791 / 31.1
1160 / 45.7
TANK
PIPING
REFRIGERANT
CHARGING MASS
STAGE OF CAPACITY CONTROL (Btu/h)
TYPE
CAPACITY/VOLUME
MILD STEEL COATED WITH ZINC
HEAD
COMPRESSOR
MAT ERIAL
MOD EL
TYPE/DRIVE
QUANTITY
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
REFRIGERANT TYPE
UNIT DIMENSION
PACKING DIMENSION
UNIT WEIGHT
NOMINAL TOTAL INPUT POWER
HYDRAULIC KIT
PUMP
SOUND PRESSURE LEVEL
EVAPORATOR
CONDENSER FAN
TYPE
NOMINAL WATER FLOW
PROPELLER / DIRECT
WATER FLOW RATE
HIGH HEAD CIRCULATOR
22 / 0.78
460 / 18.1
920 / 36.2
1270 / 50
570 / 22.4