Specifications

64
5. SELECTION PROCESS
WATER PRESSURE DROP VS FLOW RATE
Water Flow
m
3
/hr
Pump Head kPa System Head kPa
Available Head Presure
kPa
0.6 117.0 12.0 105.0
0.8 115.0 25.0 90.0
1.0 114.0 34.0 80.0
1.2 112.0 50.0 62.0
1.4 108.0 59.9 48.1
Water Flow
m
3
/hr
Pump Head kPa System Head kPa
Available Head Presure
kPa
0.7 116.0 10.4 105.6
0.8 116.0 10.8 105.2
1.0 114.0 15.2 98.8
1.3 110.0 20.9 89.1
1.5 105.0 27.9 77.1
1.8 100.0 35.2 64.8
Water Flow
m
3
/hr
Pump Head kPa System Head kPa
Available Head Presure
kPa
0.9 115.0 7.4 107.6
1.2 112.0 12.3 99.7
1.5 105.0 19.6 85.4
1.8 98.0 29.4 68.6
2.1 90.0 36.8 53.2
Water Flow
m
3
/hr
Pump Head kPa System Head kPa
Available Head Presure
kPa
1.2 168.0 26.3 141.7
1.6 162.0 26.5 135.5
2.0 144.0 34.3 109.7
2.4 137.0 49.5 87.5
2.8 113.0 62.5 50.5
Water Flow
m
3
/hr
Pump Head kPa System Head kPa
Available Head Presure
kPa
1.5 163.0 15.0 148.0
2.0 144.0 25.7 118.3
2.5 126.0 39.4 86.6
3.0 107.0 52.6 54.4
MODEL : AMAC20C/CR, A4AC20C
MODEL : AMAC25C/CR, A4AC25C
MODEL : AMAC30C/CR, A4AC30C, A5AC30CR
MODEL : AMAC40C/CR, A4AC40C, A5AC40CR
MODEL : AMAC50C/CR, A4AC50C, A5AC50CR