Specifications

49
CAUTION FOR R407C
Avoid prolong exposure of an opened compressor, or the internal part of refrigerant piping to moist
air. The POE oil in the compressor and piping can absorb moisture from air.
Heat pump
INDOOR ACK20AR ACK25AR ACK30AR ACK40AR ACK50AR
MODEL
OUTDOOR ALC20BRK ALC25BRK ALC30CR ALC40CR ALC50CR
L = 7 m 0.050 0.100 0.100 0.100 0.100
L = 10 m 0.075 0.500 0.250 0.250 0.250
L = 15 m 0.150 0.750 0.500 0.500 0.500
L = 20 m - - 0.750 0.750 0.750
L = 35 m - - 1.500 1.500 1.500
Cooling only
INDOOR ACK15B ACK20B ACK25B ACK30B
MODEL
OUTDOOR ALC15B ALC20B ALC25B ALC30B ALC30C
L  5 m 0.250 0.250 0.100 0.100 0.400
L = 7 m 0.300 0.280 0.176 0.200 0.600
L = 10 m 0.325 0.325 0.290 0.350 0.650
L = 15 m 0.400 0.400 0.480 0.600 0.900
L = 20 m - - - 0.850 1.150
Heat pump
INDOOR ACK15BR ACK20BR ACK25BR ACK30BR
MODEL
OUTDOOR ALC15BRK ALC20BRK ALC25BRK ALC30CR
L = 7 m 0.050 0.050 0.100 0.100
L = 10 m 0.075 0.075 0.500 0.250
L = 15 m 0.150 0.150 0.750 0.500
L = 20 m - - - 0.750
All refrigerant charge is in kg
Diagram shows typical charging method
ELECTRICAL CONNECTIONS
Wiring regulations on wire diameters differ from country to country. Please refer to your LOCAL ELECTRICAL CODES
for field wiring rules. Be sure that installation is complied with such rules and regulations.
GENERAL PRECAUTIONS
Ensure that the rated voltage of the unit corresponds to the nameplate before carrying out proper wiring according to
the wiring diagram.
Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit breaker for over
current protection should be provided in the exclusive line.
All wiring must be GROUNDED to prevent possible hazards due to insulation failures.
All wiring must be firmly connected.
All wiring must not come in contact with the hot refrigerant piping, compressor or any moving parts of fan motors.
12. WIRING