Specifications

45
Indoor Unit
35.0 mm
Ceiling
Board
UNIT HANGING
ACK-A ACK-B
Confirm the pitch of the hanging rod is 790.0mm X 620.5mm (ACK-A) / 600.0mm x 582.0 mm (ACK-B).
Hold the unit and hang it on the hanging rod with the nut and washer.
Adjust the unit height to 35.0 mm (ACK-A) / 25.0 mm (ACK-B) between the indoor unit bottom surface and the
ceiling surface.
Confirm with a level gauge that the unit is installed horizontally and tighten the nut and bolt to prevent unit
falling and vibration.
Open the ceiling board along the outer edge of the paper installation template.
DRAIN PIPING WORK
Drain pipe must be downward gradient for smooth drainage.
Avoid the drain pipe from up and down slope to prevent
reversal flow.
During the drain piping connection, be careful not to exert extra
force on the drain connector at indoor unit.
The outside diameter of the drain connection at the flexible
drain hose is 20 mm.
Be sure to provide heat insulation (polyethylene foam with
thickness more than 8.0 mm) on the drain piping to avoid the
condensed water dripping inside the room.
DRAIN TEST
Connect the main drain pipe to the flexible drain hose.
Feed water from flexible drain hose and check the piping for
leakage.
When the test is completed, connect the flexible drain hose to
the drain connector on the indoor unit.
Note: This indoor unit use drain pump for condensed water drainage. Installed
the unit horizontally to prevent water leakage or condensation around
the air outlet.