Specifications
21
3
rd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 37°C DB
Total capacity, TC
Interpolation Method:
x = 4.910kW
Sensible capacity, SC
Interpolation Method:
y = 3.593kW
40°C - 35°C
=
4.669kW - 5.071kW
40°C - 37°C 4.669kW - x
40°C - 35°C
=
3.378kW - 3.737kW
40°C - 37°C 3.424kW - y
Indoor DB Indoor WB
° C ° C TC
(
kW
)
SC
(
kW
)
TC
(
kW
)
SC
(
kW
)
TC
(
kW
)
SC
(
kW
)
24 15
5.071 3.737
xy
4.669 3.378
Outdoor DB ° C
35 37 40