Specifications

19
Details:
1
st
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 24°C DB, 15°C WB
Outdoor Condition: 35°C DB
Total capacity, TC
x
1
= 5.071kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 35°C Outdoor WB)*
Sensible capacity, SC
Extrapolation Method:
y
1
= 3.988kW
(b) Indoor Condition: 24°C DB, 15°C WB
Outdoor Condition: 40°C DB
Total capacity, TC
x
2
= 4.669kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 40°C Outdoor WB)*
Sensible capacity, SC
Extrapolation Method:
y
2
= 3.629kW
* This is due to 2 different conditions with same WB temperature, will have the same level of enthalpy. For
more details, please refer to psychrometrics chart
17°C - 15°C
=
3.510kW - y
1
17°C - 16°C 3.510kW - 3.749kW
17°C - 15°C
=
3.231kW - y
2
17°C - 16°C 3.231kW - 3.430kW
Indoor DB Indoor WB
° C ° C TC (kW) SC (kW)
15
x
1
y
1
16 5.211 3.749
17
5.350 3.510
24
Outdoor DB ° C
35
Indoor DB Indoor WB
° C ° C TC (kW) SC (kW)
15
x
2
y
2
16 4.807 3.430
17
4.946 3.231
Outdoor DB ° C
40
24