Specifications
General Data - Heatpump (R410A)
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.
5) SOUND SPECTRUM FOR A5CM 20/25ER IS NOT READY AT THE TIME OF PRINTING.
6) ALL SPECIFICATIONS ARE TENTATIVE SPECIFICATIONS AT THE TIME OF PRINTING. PLEASE CONSULT YOUR DEALER FOR
CONFIRMATION.
8
A5CM 20ER A5CM 25ER
A5LC 20CR A5LC 25CR
Btu/h
17500 20000
W
5130 5860
Btu/h
18500 22000
W
5420 6450
W
1723 1973
W
1493 2003
A
7.6 8.9
A
6.6 9.1
V/Ph/Hz
l/s / CFM
245 / 520 274 / 580
l/s / CFM
217 / 460 250 / 530
l/s / CFM
192 / 406 231 / 490
EXTERNAL STATIC PRESSURE (H/M/L) Pa / in.wg.
00
dBA
48 / 46 / 43 50 / 47 / 46
mm/in
218 / 8.58 218 / 8.58
mm/in
1080 / 42.52 1080 / 42.52
mm/in
630 / 24.80 630 / 24.80
mm/in
297 / 11.69 297 / 11.69
mm/in
1197 / 47.13 1197 / 47.13
mm/in
740 / 29.13 740 / 29.13
kg/lb
27 / 60 27 / 60
mm/in
19.05 / 3/4 19.05 / 3/4
l/s / CFM
614 / 1300 689 / 1460
dBA
52 52
mm/in
648 / 25.5 750 / 29.5
mm/in
855 / 33.7 855 / 33.7
mm/in
328 / 12.9 328 / 12.9
mm/in
810 / 31.9 810 / 31.9
mm/in
990 / 39.0 990 / 39.0
mm/in
415 / 16.3 415 / 16.3
kg/lb
59 / 130.1 62 / 136.7
LIQUID mm/in
6.35 / 1/4 6.35 / 1/4
GAS mm/in
12.70 / 1/2 15.88 / 5/8
kg/lb
1.40 / 3.09 1.75 / 3.86
FLARE VALVE
DEPTH
UNIT WEIGHT
PIPE CONNECTION
TYPE
SIZE
PACKING DIMENSION WIDTH
UNIT WEIGHT
CONDENSATE DRAIN SIZE
220 - 240 / 1 / 50
R410A / OUTDOOR CAP. TUBE
AUTOMATIC LOUVER (UP & DOWN)
WIDTH
DEPTH
HEIGHT
DEPTH
HEIGHT
WIDTH
DEPTH
HEIGHT
AIR FLOW
MODEL
OUTDOOR UNIT
LOW
INDOOR UNIT
NOMINAL RUNNING CURRENT (COOLING)
NOMINAL RUNNING CURRENT (HEATING)
POWER SOURCE
REFRIGERANT TYPE / CONTROL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
NOMINAL TOTAL INPUT POWER (COOLING)
NOMINAL TOTAL INPUT POWER (HEATING)
WIRELESS OR WIRED MICROCOMPUTER REMOTE CONTROL
INDOOR UNIT
MEDIUM
UNIT DIMENSION
PACKING DIMENSION
HEIGHT
WIDTH
OUTDOOR UNIT
REFRIGERANT CHARGE
CONTROL
AIR DISCHARGE
OPERATION
SOUND PRESSURE LEVEL (H/M/L)
AIR FLOW
HIGH
UNIT DIMENSION
SOUND PRESSURE LEVEL