Specifications
R-410A-3
CEILING CASSETTE A5CK-C SERIES - R-410A
A5CK10CR A5CK15CR A5CK20CR
A5LC10CR A5LC15CR A5LC20CR
Btu/h 9500 12500 17500 <18000>
W 2780 3660 5129 <5280>
Btu/h 9500 11500 17500 <18500>
W 2780 3370 5129 <5420>
COOLING W
900
830
3.09
3.35
1300
1020
2.82
3.30
1690 <1724>
HEATING W 1710 <1494>
3.03 <3.06>
3.00 <3.63>
W/W
W/W
A5CK10C A5CK15C A5CK20C
A5LC10C A5LC15C A5LC20C
Btu/h 9500 12500 17500 <18000>
W 2780 3660
1300
2.82
5129 <5280>
W 900
3.09
1690 <1724>
W/W 3.03 <3.06>
V/Ph/Hz 220-240/1/50 <380-415/3/50>
l/s / CFM 189 / 400 194 / 410 212 / 450
l/s / CFM 184 / 390 184 / 390 203 / 430
l/s / CFM 175 / 370 170 / 360 194 / 410
dBA 44 / 43 / 42 44 / 42 / 41 47 / 46 / 44
mm/in 250 (295) / 9.8 (11.6)
mm/in 570 (640) / 22.4 (25.2)
mm/in 570 (640) / 22.4 (25.2)
kg/lb 22 + 2 / 48.5 + 4.4 23.2 / 50.7 + 4.4 23 + 2 / 50.7 + 4.4
dBA 46 49 52
mm/in 654 / 25.7
mm/in 855 / 33.7
mm/in 328 / 12.9
kg/lb 31 / 72.75 35 / 77.16 59 / 130.1
FLARE VALVE
LIQUID mm/in 6.35 / 1/4 6.35 / 1/4 6.35 / 1/4
GAS mm/in 9.52 / 3/8 12.70 / 1/2 12.70 / 1/2
NOMINAL TOTAL INPUT POWER - 1Ø <3Ø>
EER - 1Ø <3Ø>
POWER SOURCE - 1Ø <3Ø>
COOLING ONLY MODEL
INDOOR UNIT
OUTDOOR UNIT
NOMINAL CAPACITY - 1Ø <3Ø>
SOUND PRESSURE LEVEL (H/M/L)
UNIT DIMENSION
( ) - WITH PANEL
HEATPUMP MODEL
OUTDOOR UNIT
HIGH
INDOOR UNIT
NOMINAL COOLING CAPACITY - 1Ø <3Ø>
NOMINAL HEATING CAPACITY - 1Ø <3Ø>
50 Hz
50 Hz
NOMINAL TOTAL INPUT POWER
- 1Ø <3Ø>
UNIT WEIGHT (UNIT + PANEL)
PIPE CONNECTION
TYPE
HEIGHT
WIDTH
DEPTH
EER - 1Ø <3Ø>
COP - 1Ø <3Ø>
LOW
220 - 240 / 1 / 50
INDOOR UNIT
AIR FLOW MEDIUM
250 (295) / 9.8 (11.6)
570 (640) / 22.4 (25.2)
570 (640) / 22.4 (25.2)
HEIGHT
WIDTH
DEPTH
OUTDOOR UNIT
SOUND PRESSURE LEVEL
UNIT DIMENSION
540 / 21.3
700 / 27.6
250 / 9.8
FLARE VALVE
SIZE
UNIT WEIGHT
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 27°C DB / 19°C WB INDOOR AND 35°C DB / 24°C WB OUTDOOR
b) HEATING - 20°C DB INDOOR AND 7°C DB / 6°C WB OUTDOOR
4) SOUND PRESSURE LEVELS ARE MEASSURED IN ANECHOIC CHAMBER, ACCORDING TO JIS C 9612 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1.4m BELOW FASCIA.