MODEL : A5ACV100 / 135CR - HEATING
68
WATER AVAIL. PUMP PUMP
HEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT
CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP
kW kW A kW kW A kW kW A m3/hr kPa W A
35 28.34 9.48 19.8 29.27 9.52 19.9 31.59 9.64 20.2 5.81 107 1049 2.0
40 24.46 10.13 21.2 25.58 10.19 21.3 28.38 10.36 21.7 5.41 134 1040 2.0
45 20.58 10.78 22.6 21.90 10.87 22.7 25.17 11.08 23.2 5.04 157 1026 2.0
50 16.71 11.44 23.9 18.21 11.54 24.1 21.96 11.80 24.7 4.64 182 1003 1.9
55 12.83 12.09 25.3 14.52 12.22 25.6 18.75 12.53 26.2 4.24 204 974 1.9
35 40.10 13.51 26.0 41.41 13.57 26.1 44.70 13.74 26.4 8.22 97 958 2.1
40 34.61 14.44 27.8 36.20 14.53 28.0 40.16 14.77 28.4 7.65 123 933 2.0
45 29.12 15.37 29.6 30.98 15.49 29.8 35.62 15.80 30.4 7.13 145 907 2.0
50 23.64 16.30 31.4 25.76 16.45 31.7 31.08 16.83 32.4 6.56 168 878 1.9
55 18.15 17.24 33.2 20.55 17.41 33.5 26.53 17.86 34.4 6.01 187 848 1.6
WATER AVAIL. PUMP PUMP
HEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT
CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP
kW kW A kW kW A kW kW A m3/hr kPa W A
35 32.72 9.73 20.3 33.77 9.84 20.6 36.69 9.88 20.7 5.81 107 1049 2.0
40 29.00 10.49 21.9 31.45 10.62 22.2 34.29 10.64 22.2 5.41 134 1040 2.0
45 27.80 11.25 23.5 29.31 11.40 23.8 31.47 11.47 24.0 5.04 157 1026 2.0
50 24.64 12.01 25.1 26.97 12.18 25.5 29.48 12.31 25.8 4.64 182 1003 1.9
55 22.14 12.78 26.7 24.68 12.96 27.1 27.08 13.15 27.5 4.24 204 974 1.9
35 46.29 13.87 26.7 47.78 14.02 26.8 51.91 14.08 27.1 8.22 97 958 2.1
40 41.03 14.95 28.8 44.50 15.14 28.9 48.51 15.16 29.2 7.65 123 933 2.0
45 39.33 16.04 30.9 41.47 16.25 31.1 44.53 16.36 31.5 7.13 145 907 2.0
50 34.87 17.13 33.0 38.16 17.36 33.2 41.71 17.55 33.8 6.56 168 878 1.9
55 31.32 18.21 35.0 34.92 18.48 35.3 38.32 18.75 36.1 6.01 187 848 1.6
WATER AVAIL. PUMP PUMP
HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT
CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP
kW kW A kW kW A m3/hr kPa W A
35 42.37 10.00 20.9 47.99 10.09 21.1 5.81 107 1049 2.0
40 39.62 10.87 22.7 44.91 11.01 23.0 5.41 134 1040 2.0
45 36.71 11.73 24.5 41.84 11.93 25.0 5.04 157 1026 2.0
50 34.14 12.60 26.4 38.76 12.85 26.9 4.64 182 1003 1.9
55 31.39 13.46 28.2 36.53 13.77 28.8 4.24 204 974 1.9
35 59.94 14.26 27.4 67.90 14.39 27.7 8.22 97 958 2.1
40 56.06 15.49 29.8 63.55 15.70 30.2 7.65 123 933 2.0
45 51.94 16.72 32.2 59.19 17.07 32.9 7.13 145 907 2.0
50 48.30 17.96 34.6 54.84 18.32 35.3 6.56 168 878 1.9
55 44.42 19.19 36.9 51.69 19.72 38.0 6.01 187 848 1.6
A5ACV 135CR
LEAVING WATER TEMP (°C
)
LEAVING WATER TEMP (°C
)
AMBIENT TEMPERATURE ON CONDENSOR (°C)
AMBIENT TEMPERATURE ON CONDENSOR (°C)
AMBIENT TEMPERATURE ON CONDENSOR (°C)
LEAVING WATER TEMP (°C)
-7 -5 0
4710
15 21
A5ACV 100CR
MODEL
A5ACV 100CR
MODEL
A5ACV 100CR
MODEL
A5ACV 135CR