3.9
SmartElec2 Controller
General Data
Sensor input NTC
Control Setpoint 16 to 35 ºC in steps of 1 degree
Temperature Control Proportional with 1ºC hysteresis
Minimum Power 0% to 99 %
Cycle time 2 seconds fixed
Protection 2 x high speed fuse for the protection of the heater switching devices
Fan Output 3 off Relay for High, Medium and Low Fan setting 3A max 240Vac
Connection
Screw terminals 5 for supply, 3 for heater output, 4 for fan output, 2 for
BMS (time) control, 2 for sensor input, 2 for external thermal trip, 2 for
external sensor, 2 for door
Supply 415 Vrms +/-15% 50/60Hz 5VA max.
Dimensions Program panel 146mm(L) x 85mm(W) x 38mm(D) max.
Mounting positions Program panel fixing centres 80mm x 20mm
Temperature 5 to 50 ºC operating; -20 to 65 ºC storage
Display Three 7-segment LCD red for parameter display
Push buttons 3 positive feedback tactile push buttons
3.8
Program Controller
General Data
Sensor input NTC
Protection 2 x ‘slow blow’ fuse for the protection of the heater switching devices.
Fan Output 3 off Relay for High, Medium and Low Fan setting 3A max 240Vac
Connection
Screw terminals 4 for supply, 6 for heater output, 4 for fan output, 2 for
BMS (time) control, 2 for sensor input, 2 for external thermal trip, 2 for
external door switch.
Supply 230V 1Ph or 415 3Ph dependent on model type.
Dimensions Program panel 88mm(L) x 88mm(W) max.
Mounting positions Program panel fixing centres 60.3mm
Temperature 5 to 50 ºC operating; -20 to 65 ºC storage
Display Three 7-segment LCD red for parameter display
Push buttons 3 positive feedback tactile push buttons