A: Technical Specifications
Power Requirements
Table A-6 provides minimum storage system power requirements.
Table A-7 provides additional information for the power distribution units (PDUs) in the
rack.
Table A-6 Minimum Power Requirements
Factor Requirement
Voltage Tower: 100 to 120 or 220 to 240 VAC
Rack: 200 to 240 VAC
Frequency 50 to 60 Hz
Maximum power consumption 700 VA
Typical power consumption 400 VA or less
Inrush current (25 °C (77 °F) cold start 1 PSU) 100 A maximum peak for 4ms, 25 A
thereafter at maximum voltage
Table A-7 Rack PDU Power Specifications
Factor Requirement or Specification
Ratings 200 to 240 VAC, 24 A, 50 to 60 Hz
Over-voltage category II
Maximum load per PDU 24 A
Maximum load per bank of outlet
sockets on each circuit breaker
10 A
Plug NEMA L6-30