Specifications

IMPORTANT:
1. Waste P-Trap, Water Supply Service Angle Stop Valve and 2” x 4” Electrical Plug-In Receptacle to be supplied
by others in accordance with local codes. A metallic p-trap (by others) must be used for the drain connection.
2. Provide 4” minimum clear space on fixture sides to allow for proper ventilation through cabinet louvers.
3. Water supply is 3/8” Outside Diameter copper tube. Waste is 1-1/4” Outside Diameter.
4. Completely flush supply lines of all foreign debris before connecting to fixture. Water cooler designed to not
affect taste, odor, color, or sediment. Optional water filter (Wf1) is available should any of these problems
arise from the water supply.
5. Do NOT solder copper tube when inserted into the coupler as damage to the o-ring will result.
6. All burrs must be removed from outside of cut tubes before inserting into coupler or other components.
7. Power supply must be identical in voltage, cycle and phase to that specified on the cooler data plate.
Electrical outlet and furnished power cord with plug must be used to supply power to fixture. Do NOT wire
compressor directly to the power supply.
8. This unit must be grounded per the requirements of applicable electrical codes.
9. WARNING: Warranty is voided if installation is not made following current Acorn Engineering installation
instructions and if components are assembled to the fixture that is not approved by Acorn Engineering.
10. Fixture operates within water pressure range of 20 to 105 psig. Acorn Engineering will not warranty fixtures
damaged when connected to supply lines with flow pressure lower than 20 psig or higher than 105 psig. A
pressure regulator must be furnished by others on supply line if inlet pressure is greater than 105 psig.
11. Due to cold waste water, Acorn Engineering recommends that p-trap supplied by installer be insulated to
prevent excessive condensation.
12. Per UPC 609.10- All building water supply systems in which quick acting valves are installed shall be provided
with devices to absorb the hammer caused by high pressure resulting from the quick closing of the valve.
These pressure-absorbing devices shall be approved mechanical devices. Water pressure-absorbing devices
will be installed as close as possible to the quick closing valve.
ACORN ENGINEERING FIELD SERVICE
TOLL FREE 800-743-8259 • LOCAL 626-855-4866 • FAX 626-855-4863
7020-905-001
Page 3 of 11
A172.8UBL SERIES REFRIGERATED BI-LEVEL WALL MOUNTED WATER COOLER
Note: there are no mounting changes to be made for -SO models.
Date: 04/29/15
Please visit for most current specifications.www.acorndrinkingfountains.com
INSTALLATION, OPERATIONS & MAINTENANCE MANUAL
3/8" NCT SUPPLY INLET
WASTE OUTLET FOR 1-1/4" P-TRAP
ELECTRICAL SERVICE ROUGH.
Ø3/8" HANGER BRACKET PUNCHING, 3 PLACES FOR
ANCHORING HARDWARE BY OTHERS.
Ø5/16" PUNCHING, 2 PLACES FOR ANCHORING
HARDWARE BY OTHERS.
1
3
8
"
6"
12"
TAIL
PIECE
*33"
7
1
4
"
A
6"
*15
5
8
"
A.
B.
C.
D.
E.
AIR FLOW
11"
16
5
8
"
5
1
4
"
E
18
5
8
"
20
1
2
"
D
E
B
17
3
8
"
C
6
1
2
"
6
5
8
"Typ.
9
1
4
"
6
3
8
"
4
1
4
"
7
7
8
" Typ.
BY OTHERS.
NOTES: