Full Product Manual

www.ACOPower.com
4120 Valley Blvd Walnut, CA 91789, USA
+1-626-737 1140
HY-PTK-100WPX20A
3 SAFETY PROTECTION -
-Spark-free protection.
-Reverse polarity solar and battery connection.
-Against reverse current from battery to solar panel at night.
-Over temperature protection with charging current de-rate.
-Transient overvoltage protection, a varistor or transient voltage suppressor (TVS) at the solar input and battery
output against surge voltage.
-Safety and EMC compliance
IEC/EN 60335, EN61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-4-5 FCC Class-B
EN61000-4-6, EN61000-4-11, EN61000-3-3, CISPR14-1
4 MAINTENANCE-
Occasionally, clean the case using a damp cloth and mild cleaning agent. Check with terminals without loose, rus
ty; If connecting cable is damaged, replace the cable by qualified person.
5 SPECIFICATION-
Voltage in below table are for 12V use, x 2 for 24V use.
1 Electrical Parameters
1-1 Rated solar panel amps 10/15/20 Max. AMP
1-2 Normal input Solar cell array voltage 15-22 VDC
1-3 Max. solar cell array voltage (output has no load) 25 Max. VDC
1-4
The controller lowest operating voltage at solar or battery side
8V
Min
VDC
1-5 Standby current consumption at night 5 Max mA
1-6 Maximum voltage drop-Solar panel to battery 0.25 Max. VDC
2 Charging characteristics
2-1
Minimum battery start charging voltage
3
Min
VDC
2-2 Soft start charging voltage 3-10 +/-0.2 VDC
2-3 Soft start charging current (50% PWM duty) Up to 5/7.5/10 AMP
2-4 Bulk charge
By the maximum rated current
Bulk charge level1 for Lead Crystal battery
By 100% maximum rated current charge
up to 14.4V.
Bulk charge level2 for Lead Crystal battery
By 50% rated current charge up to 14.7V
from 14.4V.
2-5
Absorption charging voltage at 25
--Lead Crystal battery 14.7 +/-0.2 VDC
--Gel type battery 14.1 +/-0.2 VDC
--AGM type battery (default setting) 14.4 +/-0.2 VDC
--WET type battery 14.7 +/-0.2 VDC
--Calcium type battery 14.9 +/-0.2 VDC
--LTO battery 14.0 +/-0.2 VDC
--LFP battery 14.5 +/-0.2 VDC