Installation guide
Power Cord and Cable Requirements
ARX
®
6000 Hardware Installation Guide 5 - 5
Where
n is the number of installed ASMs
m is the number of installed NSMs
The division by 0.88 accounts for the 88% efficiency of the power
supply.
If you want to plan for future expansion, you can budget for a total of 1704
Watts power dissipation. This is equivalent to 5812 BTUs/hour.
Power Cord and Cable Requirements
Table 5.3 lists the required cables and power cords for the switch. All cables
except the AC power cord and console cable are customer-supplied.
See Appendix A
for cable-connector diagrams and pinouts.
Qty. Cable/Cord Used on... Specification
1 per power
supply
AC power cord AC/DC Power Supply L6-20 type connectors for systems rated
at 20 A/220 Vac
1 Console cable with
RJ-45-to-DB9 adapter
Console port 100BASE-T Category 5 unshielded
twisted pair (UTP); 24 AWG
2 Ethernet cables for
connection to
10/100 Mbps Ethernet
management port (RJ-45
connector);
System Control Module
(SCM)
MGMT port
Mirror port
6 per NSM Ethernet cables for
connection to 100/1000
Mbps Ethernet.
(RJ-45 connectors)
6-port Network Services
Module (NSM)
(copper version)
a
100/1000BASE-T Category 5/6,
unshielded twisted pair (UTP) cable; 24
AWG
a.NSM Gigabit Ethernet ports support automatic MDI/MDIX cross-over. This feature automatically corrects the polarity of
the attached CAT5 cable, regardless if it is a cross-over or straight-through type. However, for this feature to work, the port
speed must be set to auto (auto-negotiate) through the CLI. When the port speed/duplex is forced (auto-negotiate is
disabled), automatic MDI/MDIX cross-over is disabled, and you must cable the port using standard cross-over or
straight-through cabling.
6 per NSM Fiber-optic cable for
connection to 1-Gbps
Ethernet.
small form-factor
pluggable (SFP) optical
connectors
6-port NSM (optical
version)
100BASE-FX (fast Ethernet)/
1000BASE-SX (Gigabit Ethernet), 850nm.
Short-reach multi-mode fiber (MMF) with
duplex LC-style connectors. Distances up
to 500m on 50/125um MMF, or 300m on
62.5/125um MMF.
Table 5.3 Required Power and Data Cables