User Manual
Cascaded PDUs
Dip switch no.
1 2 3 4 8
1st PDU
On
On
On
On
Off
2nd PDU
Off
On
On
On
Off
3rd PDU
On
Off
On
On
Off
4th PDU
Off
Off
On
On
Off
5th PDU
On
On
Off
On
Off
6th PDU
Off
On
Off
On
Off
7th PDU
On
Off
Off
On
Off
8th PDU
Off
Off
Off
On
Off
9th PDU
On
On
On
Off
Off
10th PDU
Off
On
On
Off
Off
11th PDU
On
Off
On
Off
Off
12th PDU
Off
Off
On
Off
Off
13th PDU
On
On
Off
Off
Off
14th PDU
Off
On
Off
Off
Off
15th PDU
On
Off
Off
Off
Off
16th PDU
Off
Off
Off
Off
Off
< 1.6 > IP Multi-port connection to remote PDU
Combo Cat6 IP KVM
IP KVM provides RJ-45 Multi port for the user to remotely control and manage servers & PDU togethe r.
Combo IP KVM
32 31 3 0 2 9 2 8 2 7 26 25 16 15 1 4 13 1 2 1 1 10 9
24 2 3 22 21 20 1 9 18 17 8 7 6 5 4 3 2 1
Other band IP KVM can NOT connect InfraPower PDU
Each RJ-45 Multi port connect max. 16 pcs of InfraPower PDU
To Multi port
1st level PDU 2nd level PDU 3rd level PDU
To LINK port
CAT. 5 / 6
CAT. 5 / 6
of the 1st PDU
LINK OUT
cable
L INK OUT
cable
LINK OUT
CUR RENT (A)
225
Up to 20 meters
CURRENT (A)
225
Up to 20 meters
CURRENT (A)
225
ON DIP
1 2 3 4 5 6 7 8
O N D IP
1 2 3 4 5 6 7 8
ON DI P
1 2 3 4 5 6 7 8
RE SET RE SET RE SET
To LINK port
of next PDU
( Up to 16 levels )
Dip switch setting
ON DIP ON DIP ON DIP
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Using the dip switch no. 1, 2, 3, 4 & 8