User`s manual

16
KOOLMASTER PP20-VS2 rev.00
KOOLMASTER PP20-VS2
4.8.4. Night Settings
Night functions allow changing the target
room temperature and the minimum ventila-
tion level when the night comes (refer to the
Minimum Ventilation chapter of this manual
to set the night fan speed).
Select:1.
Current Conditions (Main Menu)
Setup *
User
Day/Night
* A password may be required to access this menu.
Day Night Settings
Night SetPoint? Yes
Night Min.Vent? Yes
Night Heater Offset Yes
Day Time 6:00A h:m
NightTime 6:00P h:m
Transition 60 min
Set the following parameters:2.
Night Set Point? Select Yes” to use a
different target temperature at night; select
No” to disable this function.
Nig ht M ini m u m Ve nt i l at i on? The controller
can use a different minimum ventilation fan
speed at night. Select “Yes” to use particular
minimum ventilation night settings.
Nig ht Hea te r Offs et The controller can use
a different heating settings at night. Select
Yes” to enable these night settings.
Day Time Set the time at which day set-
tings start being used. *Accessible if a night
function is enabled above.
Night Time Set the time at which night
settings start being used. *Accessible if a night
function is enabled above.
Transition If the night set point is enabled
above, a transition is made from one set point
to the other. Set this transition time to the
desired value.
1 2 3 4 5
--- --- --- --- ---
6 7 8 9 10
--- --- --- --- ---
Min Vent. Relay Assignment
Set the status of each relay: select “2. “ if
the relay is used in minimum ventilation or
select “- - -” if it is not.
Relays 21-36 correspond to relays 1-16
of the external relay panel.
4.8.3. Variable Output Assignment
Two variable outputs can be used to provide
variable-speed ventilation. If they are used,
assign each of them to proper fan stages.
Select:1.
Current Conditions (Main Menu)
Setup *
Relays
Variables**
* A password may be required to access this menu.
** Accessible if variable outputs are enabled (sec. 4.5).
Fan Variable Assignment
Fan Stage 1 Variable 1 Var
Variable 2 Var
Fan Stage 2 Variable 1 On
Variable 2 Off
Set the output status separately for each 2.
fan stage in use:
Var The variable fan output is assigned to
the fan stage and operates in variable mode:
when the stage starts, the variable fan starts
running at its minimum intensity. The fan
intensity gradually increases as the room
temperature increases.
On — The variable fan output is assigned to
the fan stage and operates in on/off mode:
the fan runs at 100% when the fan stage is
on and stops when the stage is off.
Off — The variable output is not assigned.
If the last fan stage uses a variable
output, the output must use the on/off
operating mode. Do not set the operat-
ing mode of the last fan stage to the
variable mode.
Tunnel 1-2 / inlet 1-2 / natural curtains 1-2
Relays 7-8 and relays 15-20 have specially
been designed for the connection of actua-
tors. When actuators are connected to these
relays, their open and close relays can never
be activated at the same time.
Feeding output Feeder relays are used to
stop fee ders whe n a fee der run time alarm oc -
curs. These normally closed relays open when
the alarm condition is detected. *Accessible if
the feeder alarm condition is enabled (sec. 12.3).
Backup relay The backup relay box relay is
a normally closed relay which opens in case
of a power failure.
Shutoff fans in natural ventilation It is
possible to shutoff some fan output when
the controller enters in natural ventilation
(on/off fans and variable fans). Refer to the
natural ventilation section of this manual to
get further information about this feature.
Heating stages 1-3 & Hi Fire 1-3 (opt.);
Misting output;
Soaking output;
Kool-Cel® output;
Clock outputs 1-2;
Stir fan output;
Light output.
Worksheet showing default relay assign-
ment and empty templates are available
the end of this manual.
4.8.2. Assigning Min. Vent. Relays
This procedure shows how to assign on/off
relays to minimum ventilation cycles. Cho-
sen relays will switch during the “On Time
portion of minimum ventilation cycles. Refer
to section 6.1 for further information about
minimum ventilation cycles.
Select:1.
Current Conditions (Main Menu)
Min. Vent.
MinV Relays*
* Accessible if the Minimum Ventilation Relay status
option is enabled in section 6.1.2. A password may also
be required to access this menu (section 4.2).