Installation guide

85
PP-32
KOOLMASTER PP-32 REV.04
On-Time when the humidity is at or above RH Set Point + 10% as shown
below. Set the dipswitch #6 to ON to use this function.
Set the function to "18.RH Compensation" from the main menu
using the navigation buttons then press the right-arrow key. Note
that this menu only appears if the relative humidity sensor has been
enabled during the installation setup (see sec. 5.14.3).
Use the navigation buttons in order to select the "Heater On time"
display.
Use the adjustment buttons to set
the Heater's On-Time to the desired
value. This is the minimum heater's
On-time when the compensation
starts.
Press the down-arrow key once to
select the "AddHeat On time"
display.
Use the adjustment buttons to set added On-Time to the desired
value.
Press the down-arrow key once to select the "Heater Off time"
display.
Use the adjustment buttons to set the Heater's Off-Time to the
desired value.
RH set point % 65
Mist shutoff % Off
Heater On time 15
AddHeat On time 30
Heater Off time 60