Installation guide
84
PP-32
KOOLMASTER PP-32 REV.04
RH Compensation
Add Min Vent 30
RH set point % 65
Mist shutoff % 90
5.15.3.3 Adjusting Mist or Kool-Cel Shutoff
When the humidity level is too high, Kool-Cel or mist units are shut off to
avoid increasing the humidity level any further. This means that the fan
stage outputs that operates in timer mode stop operating whenever the
humidity level exceeds the mist shutoff limit. This limit ranges from 25%
to 100% (Off) of humidity. Set the dipswitch #5 to ON to activate this
function.
Set the function to "18.RH Compensation" from the main menu
using the navigation buttons then press the right-arrow key. Note
that this menu only appears if the relative humidity sensor has been
enabled during the installation setup (see sec. 5.14.3).
Use the navigation buttons in order
to select the "Mist Shutoff" display.
Use the adjustment buttons to set
the mist shutoff humidity level to the
desired value.
5.15.3.4 RH Compensation on Heaters' On-Time
Heaters can be activated in timer mode to compensate for a high level of
humidity. As the humidity level increases, the heaters' On-Time increases
proportionally to compensate for the change. The heaters reach their full
COMPENSATED
ON TIME
SECONDS
RELATIVE
HUMIDITY (RH)
HEATERS START
IN TIMER MODE
THEIR REGULAR
ON TIME
0 SEC
RH SET POINT
ON TIME
THE DELAY IS ADDED
TO THE REGULAR
HEATERS’ ON-TIME
ADDED
TIME
HUMIDITY COMPENSATION ON HEATERS