Specifications

92
Tech Support: 855-ONE-ZURN
www.zurn.com
Typical InstallationX Ref
Potable Water Expansion Tank WXTP Series
Features Applications
14 gal. – 85 gal.
Bladder type expansion tank for water heaters
Maximum pressure 150 psi
Maximum water temperature 200°F
Factory air pre-charge – 40 psi
Free standing base mounted
5 year warranty
IAPMO
®
Listed
NSF
®
listed
For Additional Information, Ask For WXT-WXTP or visit our web
site.
Designed for installation on potable water lines between the backflow preventer or pressure
reducing valve and the water heater to protect against water thermal expansion. When sys-
tem pressure increases, water enters the tank’s bladder which expands into the pre-charged air
chamber, keeping system pressure below the relief valve setting.
Water pressure reducing valve (Model NR3)
Temperature & pressure relief valve (Model TP1100A)
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted on the cold water supply and at least 18”
from the cold water inlet to the heater.
NOTE: If incoming water pressure is above 40 psi, the pre-charge pressure of the expansion tank should be adjusted to equal the incoming water pres-
sure, not to exceed 80 psi.
Pressure relief valve (Model P1000A)
Reduced pressure backflow preventer (Model 975XL)
Accessories
SEIRES V NOITALLATSNI PTXW LEDOMNOITALLATSNI PTXW LEDOM
T&P VALV
E
DIRECTION OF FLOW
HOT WATER
HEATER
MODEL WXTP
HOSE BIBB
MODEL NR3
WATER PRESSURE
REDUCING VALVE
DRAIN
MODEL 975XL
T&P VALVE
DIRECTION OF FLOW
HOT WATER
HEATER
MODEL
WXTP
HOSE BIBB
MODEL NR3
WATER PRESSURE
REDUCING VALVE
DRAIN
MODEL 975XL
WILKINS FLEXCON AMTROL WATTS STATE SPARCO BELL&GOSSETT WESSELS
WXTP-50V WH-50V ST-30V DET-35 ETC-15 TX-30V PT-30V TXC-30V
WXTP-75V WH-75V ST-42V ETC-20 TX-42V PT-42V
WXTP-120V WH-120V ST-60V ETC-36 TX-60V PT-60V
WXTP-165V WH-165V ST-80V TX-80V PT-80V
WXTP-235V WH-235V ST-180V TX-180V PT-180V
WXTP-320V WH-320V ST-210V ETC-86 TX-210V PT-210V
Miscellaneous Plumbing Products