Specifications

8
Tech Support: 855-ONE-ZURN
www.zurn.com
Model 500 Union end connection standard and available
1/2” through 2” in FNPT
Model 500C Union end connection, 1/2” through 2” female
copper sweat
Model 500HR Spring range is 75-125 psi, factory set at 85 psi;
field set 2
1
/
2
” – 3”
Model 500HLR Spring range is 10-125 psi, factory set at 50 psi;
field set 2
1
/
2
” – 3”
Model 500HT For high temperature application, up to 210°F.
Model 500L Less built-in by-pass. (1/2” – 2”)
Model 500LPV Same as 500HT except spring range is
10-35 psi, factory set at 20 psi
Model 500LPC Spring range is 10-35 psi, factory set at 20 psi.
Model 500SW Chrome plated internals for salt water
Model 510 Rated for 400 psi and spring range is
75 - 125 psi, factory set at 85 psi; field set
2
1
/
2
” – 3”
Model 500SC Sealed cage bell and stainless steel adjusting
screw. For below-ground and indoor
applications
Model 500XL California AB 1953 compliant
For Additional Information, including flow curves, reference
WK-RC catalog or visit our web site.
1/2”, 3/4”, 1”, 1
1
/
4
”, 1
1
/
2
”, 2”, 2
1
/
2
”, 3”
Pressure rated 300 psi
Spring range 25 to 75 psi; factory set at 50 psi
Field set 2
1
/
2
” – 3”
Maximum temperature 180°F
All bronze body and bell housing provides durability and long life
Built-in by-pass prevents buildup of excessive system pressure caused by
thermal expansion (1/2” – 2”)
Nylon reinforced Buna-N diaphragm
Balanced piston design
May be installed in any position
All internal parts corrosion-resistant
Serviceable in-line
Available tapped and plugged for gauge (optional)
Available tapped with gauge (optional)
Available with BSP threads 1/2” through 2” (optional)
ASSE
®
Listed 1003 (1/2"-2
1
/
2
"), IAPMO
®
Listed (1/2"-2"), CSA
®
Certified
(1/2"-2"), City of Los Angeles (1/2"-3")
The model 500 is the workhorse of the Wilkins pressure reducing valve line up. The model 500
exhibits the highest flow rates of the entire Wilkins regulator line, making it most suitable for commercial,
industrial, and irrigation applications that demand high flow rates with minimal fall-off. The model 500
is available in 10 – 35 psi, 25 – 75 psi, 75 – 125 psi, and 10 – 125 psi adjustment ranges. All
1/2” to 2”
500’s are equipped with a union inlet and female NPT outlet, while the 2
1
/
2
” and 3” are provided with
female NPT on the inlet and outlet.
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted in accordance with the manufacturer’s
instructions and the latest edition of the Uniform Plumbing Code. The assembly shall be installed with sufficient clearance for testing & maintenance.
The Model 500 may be installed in any position. If installed in a pit, vault, or indoors, specify the “SC” sealed cage option. Multiple installations are
recommended for wide demand variations or where the desired pressure reduction is more than 4 to 1 (ie: 200 psi inlet reduced to 50 psi outlet).
CAUTION: Anytime a reducing vale is adjusted, a pressure gauge (Model HGI-25) must be used downstream to verify correct pressure setting. Do not
bottom out adjustment bolt on bell housing.
OptionsTypical InstallationX Ref
500 Series
Features ApplicationsAccessories
Pressure gauges (Model 92-25A 1/2", 3/4") (Model 92-25 1" – 3")
WILKINS WATTS CONBRACO
500 223, N223B 36H
500HR 223HP, N223BHP
Water Pressure Reducing Valves