Specifications

64
Tech Support: 855-ONE-ZURN
www.zurn.com
Typical Installation Typical Installation
Connect 120 VAC input to terminals T10 - T12. Connect backflow supervisory switch to T8 and T9. Connect T3 and T4 to solenoid shut off valve ZW106
to turn off water supply when alarm triggers. Terminals T5 - T7 can be connected to an external alarm panel. T1 and T2 can be used to power an exter-
nal high voltage alarm. Housing designed for use with flexible watertight conduit.
Electric Solenoid Timer Model EST
Features Applications
Designed for installation with Wilkins Model 375MS or 475MS RPZ with
Monitor Switch feature and Model ZW106 solenoid control valve
Input – 120 VAC 5A
Relay power – 1.1 VA at 24 VAC
Low voltage power supply – 24 VA at 24 VAC
Contact closure – 3A at 120 VAC
120 VAC output – 3A
24 VAC Output – 0.7A
External top mounted power and alarm lights
Wall and valve mounting brackets included
Enclosure size 7.5H x 7.5W x 5.0D
UL
®
Listed (housing)
CSA
®
Certified (housing)
For Additional Information, Ask For BF-EST or visit our web site.
Designed for installation on potable water lines to shutdown system flow should the relief
valve open on a reduced pressure principle backflow assembly. The EST is designed for instal-
lation in conjunction with the Wilkins Model 975XLMS, 375MS, or 475MS RPZ with monitor
switch feature and Model ZW106 solenoid control valve with 24vac solenoid. In the event of
a backflow condition with discharge from the relief valve occurring, the EST de-energizes the
solenoid on the control valve shutting down system flow. Standard operation is for the water
to shut off during a power failure. The EST system should not be installed where water must
remain on at all times. EST output can also be used to trigger high voltage alarms, warnings
lights, start sump pumps, etc. Ideal for use in mechanical rooms, basements and enclosures
where undetected relief valve discharge could potentially cause water damage.
ZW106 Solenoid operated control valve (special order
with 24 VAC solenoid)
375MS/475MS Model 375 or Model 475 with integral relief
valve monitor switch
Accessories
imer
E
S
lectric
olenoid
T
12" MIN.
30" MAX.
FUSE
T7
T6
T5
T4
T3
T2
T1
N/C
COMMON
N/O
24 VAC
120 VAC
TIMER
POWER
24 VAC COM
120 VAC COM
T12
T11
T10
T9
T8
GROUND
LINE 2
LINE 1
SWITCH
SWITCH
TEST
power light
alarm light
imer
E
S
lectric
olenoid
T
12" MIN.
MODEL 375MSOSY
MODEL EST
MODEL ZW106
30" MAX.
375MS with ZW106 Solenoid Control Valve and EST
Electronic Solenoid Timer
DIRECTION OF FLOW
Backflow Preventer Accessories