Typical InstallationX Ref
Spill Resistant Pressure Vacuum Breaker 460 Series
Features Applications
3/8”, 1/2”, 3/4”, 1”
Spill resistant feature for indoor use
Maximum pressure 150 psi
Temperature range 33°F – 180°F
Hydrostatic test pressure 300 psi
Easy maintenance - bonnet & seat removal tool built into canopy
Replaceable modular thermoplastic cartridge
ASSE
®
Listed 1056, IAPMO
®
Listed, CSA
®
Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
In some applications that require a pressure vacuum breaker, spillage from the PVB would be
objectionable. The Wilkins 460 spill resistant vacuum breaker was created to prevent such
spillage. Designed to prevent contamination of the potable supply due to backsiphonage, the
460’s unique operation causes the air inlet to close before water passes the check valve. This
operation makes the 460 resistant to leakage from the air vent during start-up. All internal com-
ponents are in modular form, making the 460 an easily repaired assembly.
ZW3 Winterizer
Water hammer arrester (Model 1250)
Quick test set (QT-SET)
Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be installed in accordance with the manufacturers’ in-
structions and the latest version of the Uniform Plumbing Code. The critical level mark on the assembly shall be mounted at a minimum of 12” (305mm)
above the highest downstream piping or outlet. Install with sufficient side clearance for testing and maintenance. The installation shall insure that no part
of the assembly can be submerged. A spill-resistant pressure vacuum breaker cannot be installed where back-pressure could occur.
For Additional Information, Ask For BF-460 or visit our web
site.
Accessories
INDOOR INSTALLATIONOUTDOOR INSTALLATION
12" MIN.ABOVE
MODEL 460
MODEL 460
HIGHEST OUTLET
DIRECTION OF FLOW
DIRECTION OF FLOW
12" MIN. ABOVE
HIGHEST
OUTLET PIPING
WILKINS WATTS CONBRACO
460 008PCQT 4W-500
Backflow Preventers