Reduced Pressure Principle 475/475V Series Pat. No. 5,913,331
2
1
/
2
”, 3”, 4”, 6”, 8”, 10”
Reduced pressure principle backflow preventer consisting of a pressure
differential relief valve located between two independently operated
spring-loaded center guided check valves
Available in up/down (475) or up/up (475V) configuration
Complete with two flange-ended non-rising stem full port grooved by
flanged end gate valves and four resilient seated ball valve test cocks
Lightweight, ductile iron construction with FDA approved fusion epoxy
coat inside and out
Utilizes a patented center-stem guided compound check™ closure
(Pat. No. 5,913,331)
Modular check design utilizing lead-free
engineered plastic (Noryl
®
) and stainless
steel
Temperature range 33°F – 140°F
Maximum pressure 175 psi
2
1
/
2
” and 3” sizes use 375 with 90° elbows
ASSE
®
Listed 1013, UL
®
Classified, FM
®
Approved, C-UL
®
Classified,
IAPMO
®
Listed, CSA
®
Certified, AWWA Compliant
Approved by the Foundation for Cross-Connection Control and Hy-
draulic Research at the University of Southern California
Model 475 Flange x flange, NRS gate valves
Model 475L Less gate valves (grooved body connections).
Model 475G Grooved end NRS gate valves
Model 475FG Flanged inlet NRS gate connection and grooved
NRS outlet gate connection
Model 475OSY Flanged end OS&Y (outside stem and yoke) gate
valves. For fire protection applications
Model 475OSYG Grooved end OS&Y gate valves
Model 475PI Supplied with post indicator gate valves
Model 475V Vertical configuration (flow up)
Model 475VG Same as 475V except with grooved end NRS gate
valves (vertical configuration)
Model 475VFG Same as 475V except with flanged inlet NRS gate
connection and grooved outlet gate connection
(vertical configuration)
Model 475VPI Same as 475V except supplied with post
indicator gate valves
Model 475BGVIC Supplied with groove x groove tampered
Victaulic
®
butterfly valve (4” – 8”)
Model 475VBGVIC Same as 475BGVIC except vertical configuration
(4” – 8”)
To create a part number to fit your needs, see page 3
For Additional Information, reference WK-BPC catalog or visit
our web site.
OptionsTypical InstallationX Ref Features
The Wilkins 475 / 475V series reduced pressure principle assemblies are the perfect answer for cramped
installations that rule out a traditional horizontal valve. The 475, with its “N” pattern design, is the perfect
valve for use in retrofit applications where a horizontal valve will just not fit. The 475V allows for a vertical
up-up flows, and can be situated in very small closets or mechanical rooms. Both valves offer the low
head loss provided by the patented Wilkins Compound Check
®
, while providing high hazard protection
against both backsiphonage and backpressure. Using the valve setter, installation is simple and easy and
very cost-effective.
Air gap (Model AG)
Thermal expansion tank (Model XT)
Valve setter (Model FLS or MJS or MJFS)
OS&Y gate valve supervisory switch (OSY-40)
Soft seated check valve (Model 40XL)
Electronic Solenoid Timer (Model EST)
Solenoid control valve (ZW106)
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Accessories Applications
475G
475VG
3” 475
DIRECTION OF FLOW
12" MIN.
30" MAX.
WILKINS VALVE
SETTER
PROTECTIVE
ENCLOSURE
AIR GAP
DIRECTION OF FLOW
DRAIN
AIR
GAP
DIRECTION OF FLOW
12" MIN.
30" MAX.
WILKINS VALVE
SETTER
PROTECTIVE
ENCLOSURE
AIR GAP
MODEL 475G MODEL 475BGVIC MODEL 475VG
Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions
and the latest edition of the Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at
a minimum of 12” (305mm) and a maximum of 30” (762mm) above adequate drains with sufficient side clearance
for testing and maintenance. The installation shall be made so that no part of the unit can be submerged.
WILKINS FEBCO
475 880
475V 880V