Specifications

42
Tech Support: 855-ONE-ZURN
www.zurn.com
Breakaway hydrant lock for barrel lock (BHLB)*
Breakaway hydrant lock for padlock (BHLP)*
Test cock lock (Model TCL24)
*Locks not included
Hydrant Backflow and Meter Combination RPHBM
3”
Consists of a 3” hydrant meter and 3” check valves allowing for increased
flow up to 650 gpm as compared to 2" check valves with a capacity of
250 gpm
Single body construction. Water meter plus reduced pressure principle
backflow preventer encased in a single body design
Unitized a lightweight exterior epoxy powder-coated (blue) hard-anod-
ized aluminum body design results in a short lay length (26
1
/
2
") and light
weight (54 lbs) product ideal for temporary installations
Integral inlet screen to protect against damage by larger debris
Lifting handles allow for quick installation to fire hydrant
Includes adjustable support stand for positive support
2
1
/
2
” brass inlet swivel fitting for fast installation
Class II turbine-type meter ensures accurate measurement
Straightening vanes for accurate meter measurement
Meets the requirements of ANSI/AWWA C701-88 class II
(for meter only)
Max intermittent flow rate 650 gpm
Max continuous flow rate 450 gpm
Min flow rate 2
1
/
2
gpm
Maximum working pressure 175 psi
Max temperature 140°F
RPHBM 2
1
/
2
" FNH Swivel x 2 1/2" MNH
RPHBMGV Outlet slow closing shutoff valve
RPHBMCFM With cubic foot meter
Many other options available, consult Wilkins.
For Additional Information, Ask For RPHBM or visit our web
site.
OptionsTypical Installation Features
The Wilkins RPHBM was designed to help water purveyors increase income through the accurate
measurement of water while protecting the potable water supply at the same time. Designed to
measure the quantity of water used in temporary installations such as connection to a fire hydrant,
RPHBM allows for rapid refill of water trucks used for job site dust abatement and soil compaction.
Equipped with 2
1/2” fire hydrant inlet, and a 21/2” fire hose outlet, the RPHBM can hit inter-
mittent flow rates as high as 650 gpm in a short, light-weight package. The RPHBM is designed to
provide backpressure and backsiphonage protection where a health hazard exists, while allowing
the water purveyor to accurately determine that amount of water used for proper billing.
Accessories Applications
HYDRANT
RV DISCHARGE
PORT
DIRECTION OF FLOW
VENT
HPM
AWWA CLASS II
6363782 B1 USA PAT
FHD
BREAKAWAY HYDRANT LOCK FOR PADLOCK
(MODEL BHLP)
OPTIONAL GATE VALVE
(MODEL RPHBMGV)
BREAKAWAY HYDRANT LOCK FOR BARREL LOCK
(MODEL BHLB)
Backflow Preventers