Specifications
38
Tech Support: 855-ONE-ZURN
www.zurn.com
Reduced Pressure Principle with 90° Elbows 975XLSE Series
• 3/4”, 1”, 1
1
/
4
”, 1
1
/
2
”, 2”
• Reduced pressure principle backflow preventer consisting of a pressure
differential relief valve located between two independently operated
spring-loaded center guided check valves, wye pattern body
• Complete with two full port resilient seated ball valves for shut-off and
four resilient seated ball valve test cocks
• 90° street elbows allow for easy retrofit in space restrictive areas
• Short laying length
• Bronze body construction
• Replaceable Noryl
®
check seats
• Silicone check valve disc standard
• Entire unit serviceable in line
• Temperature range 33°F – 180°F
• Maximum pressure 175 psi
• Available with stainless steel handles (optional)
• ASSE
®
Listed (1
1
/
4
” – 2”), AWWA Compliant, IAPMO
®
Listed,
CSA
®
Certified
• Approved by the Foundation for Cross-Connection Control and
Hydraulic Research at the University of Southern California
Model 975XLSE FNPT x FNPT with street elbows (3/4” & 1”)
Model 975XLSEU Full port quarter turn union ball valves
Model 975XLSEFT Supplied with fast-test test cocks
For Additional Information, reference WK-BPC catalog or visit
our web site.
OptionsTypical InstallationX Ref Features
The 975XLSE provides the flexibility of allowing a vertical up-up and up-down installation,
while keeping the installation foot print small. The use of street elbows installed between
the valve body and the shut-off valves, yield the narrow footprint. The 975XLSE is a perfect
valve for use in high hazard backpressure or backsiphonage irrigation installations where a
large backflow enclosure would detract from the aesthetics of the landscape.
Air gap (Model AG)
Thermal expansion tank (Model XT)
Soft seated check valve (Model 40XL)
Water hammer arrestor (Model 1250)
Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions
and the latest edition of the Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at
a minimum of 12” (305mm) and a maximum of 30” (762mm) above adequate drains with sufficient side clearance
for testing and maintenance. The installation shall be made so that no part of the unit can be submerged.
Quick test set (QT-SET)
Test cock lock (Model TCL24)
Ball valve monitor switch (Model BVMS)
Accessories Applications
DIRECTION OF FLOW
DIRECTION OF FLOW
MODEL 975XLSE
MODEL 975XLSE
WILKINS FEBCO
375XLSE 825YA
Backflow Preventers