Specifications
31
Tech Support: 855-ONE-ZURN
www.zurn.com
OptionsTypical InstallationX Ref
Model 450DA Flanged end OS&Y gate valves
Model 450DAL Less end OS&Y gate valves, grooved
connections
Model 450DAG Grooved end OS&Y gate valves
Model 450DALM Less water meter
Model 450DABGVIC Supplied with groove x groove tampered
Victaulic
®
butterfly valves (4” – 8”)
Model 450DAFG Flanged inlet gate connection and grooved
outlet OS&Y gate connection
Model 450DAPI Supplied with post indicator gate valve (ask
for spec sheet GV-PI)
Model 450CFM With cubic feet meter
Model 450SCFM With Sensus cubic feet meter
To create a part number to fit your needs, see page 3 for an
example
For Additional Information, reference WK-BPC catalog or visit
our web site.
Double Check Detector 450DA Series Pat. No. 5,913,331
Features Applications
• 4”, 6”, 8”, 10”
• Double check valve consisting of two independently operated spring-
loaded center guided check valves
• Standard with two flange-ended resilient wedge OS&Y (outside stem
and yoke) gate valves and four resilient seated ball valves and test cocks
• The bypass assembly consists of a 5/8” x 3/4” water meter in series with
a double check valve backflow preventer
• Lightweight, ductile iron construction with FDA approved fusion epoxy
coat inside and out
• Utilizes a patented center-stem guided Compound Check
®
closure
(Pat. No. 5,913,331)
• Modular check design utilizing lead-free engineered plastic (Noryl
®
)
and stainless steel
• For use in fire line services
• Temperature range 33°F – 140°F
• Maximum pressure 175 psi
• ASSE
®
Listed 1048, UL
®
Classified, FM
®
Approved, C-UL
®
Classified,
AWWA Compliant, CSA
®
Certified (sizes 4” & 6”)
• Approved by the Foundation for Cross-Connection Control and Hy-
draulic Research at the University of Southern California
When space is tight, and a traditional horizontal valve just will not fit, the Wilkins 450DA is the space saver
that is needed. The 450DA is an “N” pattern double check detector assembly designed to prevent back-
pressure or backsiphonage of water from the fire system into the public potable supply. While protecting
against a non-health hazard backflow condition, the 450DA provides low head loss and excellent backflow
protection through the use of the center stem guided Compound Check
®
. As is true with all of Wilkins large
diameter backflow assemblies, the 450DA is available with grooved or flanged end connections via gate or
butterfly shut-off valves.
Valve setter (Model FLS or MJS or MJFS)
Flange by groove adapter (FLA)
OS&Y gate valve supervisory switch (OSY-40)
Local codes shall govern installation requirements. To be
installed in accordance with the manufacturers’ instructions
and the latest edition of the Uniform Plumbing Code. Unless
otherwise specified, the assembly shall be mounted at a mini-
mum of 12” (305mm) and a maximum of 30” (762mm) above
adequate drains with sufficient side clearance for testing and
maintenance. The installation shall be made so that no part of
the unit can be submerged.
Quick test set (QT-SET)
Test cock lock (Model TCL24)
(450DAG Shown)
PROTECTIVE
ENCLOSURE
MODEL 450DA
12" MIN.
30" MAX.
DIRECTION OF FLOW
WILKINS VALVE
SETTER
MODEL MJFS
Accessories
WILKINS WATTS FEBCO AMES
450DA N775DCDA 876 3001SSN
876V 3001SSZ, 300(a) M&C “N”
Backflow Preventers