Specifications
105
Tech Support: 855-ONE-ZURN
www.zurn.com
Fire Hose Valves Z3000/Z3005 Series
• 2
1
/
2
”
• For use in high pressure standpipes to control pressure to individual hose
stations under both flow and no-flow conditions
• Rated up to 400 psi inlet pressure
• All bronze construction
• Model Z3000 series features female NPT inlet x male hose thread outlet
or available with grooved inlet
• Model Z3005 series features female NPT inlet and outlet
• Available in angle or in-line (globe) configurations
• All valves are adjustable and can be field or factory set
• Available with rough chrome finish
• Special hose threads available as an option
• UL
®
listed, C-UL
®
listed
Z3000 Angle type valve
Z3000IL In-line (globe type) valve
Z3000CC
With cap and chain
Z3000CH With chrome finish
Z3000SF With San Francisco hose thread (3”)
Z3000ST With specified hose thread
Z3000G Grooved inlet
Z3005 Angle type valve
Z3005IL In-line (globe type) valve
Z3005CH With chrome finish
Z3005CAP
With capped bonnet
For Additional Information, reference WK-FP catalog or visit
our web site.
OptionsTypical Installation Features
The Pressure-Tru™ Z3000 and Z3005 series pressure reducing valve is listed as a standpipe valve
for individual hose stations in class I and class III systems. Regulates pressure under both FLOW and
NO-FLOW conditions. Can be adjusted and set at the factory or field adjustable without draining the
standpipe riser.
ApplicationsX Ref
Wilkins Elkhart Giacomini
Z3000 URFA25-2.5 A202
Z3000IL A204
Pressure Reducing Fire Sprinkler and
Fire Hose Valves