Specifications
103
Tech Support: 855-ONE-ZURN
www.zurn.com
Automatic Fire Control Valves Z3004 Series
• 2
1
/
2
”
• For use in high pressure standpipes to control pressure to an automatic
sprinkler system under both flow and no-flow conditions
• Rated up to 400 psi inlet pressure
• Open-close indicating feature
• Designed for flows up to 500 gpm
• 2
1
/
2
” female inlet and outlet connections or available with grooved
options
• Available with optional integral supervisory switch
• Available in angle or in-line (globe) configurations
• All valves are adjustable and can be field or factory set
• Available with rough chrome finish
• UL
®
listed, C-UL
®
listed
Z3004 Angle type valve
Z3004IL In-line (globe type) valve
Z3004MSA With monitor switch adapter
Z3004CH With chrome finish
Z3004SS With integral supervisory switch; contact rating of 3
amps at 125VAC and a tamper-resistant cover
Z3004T Tapped & plugged inlet and outlet for pressure gauge
(not available on angle grooved body)
Z3004CAP With capped bonnet, no hand wheel assembly
Z3004G Grooved inlet / outlet connections
For Additional Information, reference WK-FP catalog or visit
our web site.
OptionsTypical Installation Features
The Pressure-Tru™ Z3004 series pressure reducing valve is listed as a floor control valve in au-
tomatic sprinkler systems as well as a standpipe valve for class I and class III systems. Regulates
pressure under both FLOW and NO-FLOW conditions. Can be adjusted and set at the factory or
field adjustable without draining the standpipe riser and fire sprinkler system.
Applications
(Shown with optional supervisory switch)
X Ref
Wilkins Elkhart Giacomini Dixon
Z3004 URFA-20-2.5 A201 FAPRAV F250
Z3004IL URFA-20S-2.5 A203 FAPRV F250
Z3004SS URFA-20-2.5-01
Z3004MSA A201/A170
Z3004ILSS URFA-20S-2.5-01
Z3004ILMSA A203/A170
Pressure Reducing Fire Sprinkler and
Fire Hose Valves