Installation Instructions

Synergize RF ILC Installation Instructions 5
Installation Notes
Relay Connection
The ILC device 24 VAC relay port is only designed to accept a maximum 5 A.
This limit applies even if the relay component supports 12 A. 24 VAC/5 A port
loads must be protected with dedicated 5 A breakers. 208-277 VAC/30 A port
loads must be protected with dedicated 30 A breakers.
RF Location
The ILC device contains an internal radio antenna intended only for outdoor
use. Install the ILC device in an area where structures, trees, or hills provide
minimum obstructions. Refer to MTU Installation Requirements (Y20255-TEB)
for additional information.
Power Source
The ILC device must be sourced from a dedicated 5 amp breaker.
Introduction
Use these instructions in conjunction with
standard utility safety guidelines and
procedures when installing Aclara’s
Intelligent Load Control (ILC) device.
Utility supplied high voltage field wiring
must use copper conductor only and have a
+90° C rating. All field wiring should
comply with local and national codes.
To ensure a rainproof seal, make sure that
the door is completely closed and screw is
fully seated. It is the installer and utility's
responsibility to ensure the door is secured
with an anti-tamper seal or lock.