Installation Instructions
Table Of Contents
Synergize RF ILC Installation Instructions 11
6. Secure the wires in place by carefully tightening the connector screws to
7.0-8.9 in-lbs.
Over-tightening the screws or allowing the connector to move while tightening
the screws may damage the connector or PC board connection.
7. Reinstall the inner cover by torquing four screws to 10 in-lbs., and close the
other door without locking it.
8. Re-apply power to the ILC device, and verify the green Power LED is on.
The amber Demand LED may be lit for at least the first five minutes.
A flashing Fault LED indicates one or more wires are connected incorrectly.
Disconnect power and examine all wiring immediately. Correct any wiring
issues before proceeding. Attempting to operate the ILC device with incorrect
wiring may cause severe damage to the unit.