Table 4.1
Product Specifications
Specification Description
Meter Hardware Version I-210+c and I-210+c RD Gen 5 platform
Meter Firmware Version
6.0.4.1
eRF I-210+c NIC (EndPoint) Hardware Version Y84092-1
Aclara RF NIC (EndPoint) Firmware Version 1.74
AclaraONE Release 1.10
MeterMate 6.10.0.166
EndPoint quiescent power consumption 1.5W
450 MHz Band antenna port output power +30.3 dBm (conducted)
450-470 MHz band receiver sensitivity
-98 dBm maximum receiver sensitivity at 10
-5
BER @ 4800 BAUD with 4GFSK modulation
having 1kHz tone separation; directed in the
most favorable heading
Frequency Band 450-470 MHz
Note: The radio is configurable to operate in numerous specific 12.5 kHz channels within the
450-470 MHz band.
Transmission Rate 4800 BAUD (which, when operated with 4GFSK
modulation, provides 9600 bps).
Antenna Impedance 50 Ohms
Antenna Gain The antenna gain averages -6 dBi (or higher)
across the front half of the meter, averages
-13.1 dBi (or higher) across the back half of
the meter, with a minimum gain of -16 dBi (or
better) along any azimuth.
Note: Mounting the meter in an environment near metal will affect the antenna pattern.
Altitude
Operation to 5000 ft. elevation above sea
level
NIC Operating Temperature Range
-40° to +85°C (inside the meter), 0 to 95%
relative humidity (non-condensing)
Note: Refer to the Meter User Guide, Chapter 2, Operating Range and Ratings for the I-210+c
meter ratings.
Last Gasp repetition
Up to 6 messages over the course of 20
minutes when starting with fully charged
super capacitors (supercaps)
Real Time Clock power ride-through
capability
24 hours
Daily Shift Message Capacity
32 measurements
On-request Read message Capacity
4 measurements
Demand Reset Message Capacity
32 measurements