Installation Notes
The GE kV2c meter integrated with the Synergize RF module is a plug-for-plug
meter replacement designed to be inserted into a number of standard socket meter
bases. To install the integrated meter, simply remove the existing meter and insert
the integrated meter in its place. Record the final reading of the replaced meter as
per standard utility practices.
The blue LED is set to flash on the meter to provide a visual indication that the
meter has powered on.
If a time set command is received from at least one DCU with a matching Network
ID within 5 minutes of powering up, the blue LED light stops flashing and remains
solid for 2 minutes, and then turns off.
However, if the valid time set command is NOT received within 5 minutes, the
flashing blue LED turns off. If this occurs, note that the Synergize RF module did
not make a valid network connection. Try to install another meter at this location.
If the condition persists with the second meter record the meter number, and note
that the meter was left with a flashing blue LED. Also note if you are unable to
successfully install a meter at this location. If you have questions, please contact
Aclara Support at
support@aclara.com or call 1-800-892-9008.
N
OTE
You will see the blue LED flashing on the right front side of the meter
underneath the meter nameplate.
Upon verification of normal operation, record all appropriate information,
including digital register reading, before completing installation.