Chapter B • Local Menu “WALL” Command Information
D C U M a i n t e n a n c e a n d O p e r a t i o n M a n u a l 63
MyDNS Server2: 192.168.1.1
Defined by the network; this is the IP Address of a secondary AclaraOne server. This
number is auto-generated with DHCP on. When DCHP is off, this IP address will be
entered based on customer networking requirements.
MyMAC Address:
00:19:2b:00:5e:54
MAC ID address of the Ethernet/fiber daughter board.
MyMTU Size: 1514
MTU Size is the maximum size of the Ethernet packets the DCU can transmit. Defaults to
1514 for Ethernet. Minimum size allowed is 512.
Auto Negotiate ON
This allows the system to automatically set the Ethernet network speed (i.e. 10 Mbps or
100 Mbps) based on connection. Problems can arise if either side hard sets its rate to
100Mbps. Manual setting of the speed should not be needed unless auto-negotiating is
failing (perhaps due to very old switch).
MyIP Address (cellular):
10.80.1.8
This is the IP Address of the Cellular device after the SIM card has been activated.
AC/DC Power Supply (9985H)
Version of the power supply/charging board. 9975H is the legacy board and would
provide slightly different parameters
S/N: 00000000
Serial number of the power supply. All 9985H boards will be 00000000. 9975H units will
have a unique ID.
H/W: A This is the hardware version of the power supply board, if applicable.
Battery Hardware settings This is only applicable for the 9985H board.
Battery Size = 41(Ah)
Size of the installed battery. Factors into the State of Charge (SoC) calculation. The
default size is 41Ah if battery count equals 1, but will default to 30Ahrs if battery count
equals 0. Value can be changed to 30Ah if appropriate.
Battery Count = 1
Defaults to "1". Check to ensure this is correct. At this time, the DCU only supports a
single battery, but menu allows battery count to be set to 0, 1, or 2.
Cell count = 6
Lead Acid battery detection results in "6". Value is based on the detection of a supported
battery. This allows for future support for combinations of different battery sizes.
AC powered = YES
Indicates whether the DCU is detecting AC power. AC Power requires at least 2 cycles to
detect. AC power will detect 50/60Hz 120VAC +/- 20%.
Solar powered = NO
Indicates whether the DCU is detecting DC power. DC power detection requires an input
voltage between 10.9VDC-23VDC (maximum 5.9amp ratings).
Battery type = Lead-Acid Reports the Battery chemistry type the charging board is set for. Default is Lead-Acid.
Freeze protection settings: This only applies to the 9985H board.
Field Example Description