50 D C U M a i n t e n a n c e & O p e r a t i o n M a n u a l
Troubleshooting
Power Supply Board
Verify the power cables harness from the battery is attached.
Verify the board is securely seated.
Check LED activity lights as indicated in the following image and table.
LED D2 (Blue) LED D3 (Red) LED D4 (Green) LED D9 (Green)
Solid on - initial
boot-up
Off - not used
(normal)
Flashing -
transmitting
(normal)
On - 3.3 VDC
power present to
board (normal)
Flashing - boot-up
completed (normal)
Off - not
transmitting
Off - no power to
board
LED State Description
1
Off No power to PCB
On Power supply board is booting
Flashing 1x/sec Power supply board is running
Flashing 4x/sec Firmware upgrade is in progress
3
Off Solar panel or AC charger is switched off or
not connected to the DCU
On Solar panel or AC charger is connected to the
DCU
LED 1
Incoming AC
Incoming DC voltage from battery harness
LED 3
Thermistor
connection