30 Universal Metering Transponder for kV2c™ Meter User Guide
TWACS Installation
N
OTE
If a power down occurs during calibration and the real-time clock has a valid
time, the invalid time sync would need to be sent again.
Options
If a kV2c meter supports KYZ/Form A functionality, the operations of the
UMT-C-KV module shall not, in any way, adversely affect the performance of the
KYZ/Form A inputs or outputs.
TWACS Installation
This section provides an overview of the integration and installation process and
procedures for verifying that the meter is properly reading and communicating
with the network.
Type and Model Numbers
A complete listing of all DCSI Remote Communications Equipment and the
applicable meters can be found on the TWACS portal in the Transponder Type and
Model Matrix. If you do not have access to the portal, contact Customer Care at
Care@twacs.com for assistance.
The following table provides module type, model number, class, voltage, service,
and Energy per Count for each form that is usable with the transponder and meter.
Table 2.8
Model number, class, meter form, voltage, service type, and energy
Type 101
Model
Number Class Form Voltage Service
Energy
Per
Count
1 200 1S 120V-480V
Autorange
2-Wire Single Phase Self-Contained 0.0025
2 200 2S 120V-480V
Autorange
3-Wire Single Phase Self-Contained 0.0025
3 320 2S 120V-480V
Autorange
2-Wire Single Phase Self-Contained 0.00375
4 20 3S 120V-480V
Autorange
2-Wire Single Phase Current
Transformer Rated
0.0025
5 20 4S 120V-480V
Autorange
3-Wire Single Phase Current
Transformer Rated
0.00025
6 20 45S 120V-480V
Autorange
3-Wire Polyphase Current
Transformer Rated
0.00025
7 20 36S 120V-480V
Autorange
4-Wire Polyphase Current
Transformer Rated
0.00025