User's Manual

TWACS
®
- ORION
®
for CENTRON
®
Meter User Guide 29
Chapter 2 • Testing, Troubleshooting, and Maintenance
Figure 2.4
TWACS serial number location
8.
The RTS will attempt to communicate with the TWACS-ORION
system. A series of setup screens will appear.
Figure 2.5
RTS setup screens
The RTS begins with a firing angle of 14 degrees and gradually
increases until it fails or until communication setup is complete.
Table 2.2
RTS communication success or failure
If the
communication…
Then…
fails the firing angle sequence will end at 26 degrees and
start over at 14 degrees. Check the electrical
connections and verify that the correct TWACS
serial number was entered. If there is no problem
with the setup, replace the TWACS-enabled meter
and retry the communication setup. Return the
failed meter to the meter shop. Refer to Return
Procedures on page 31.
succeeds the following screen appears: